34
ACS550 User’s Manual
Start-up, control with I/O and ID Run
Select the motor identification method (parameter
The default value 0 (
OFF
/
IDMAGN
) using the identification magnetization is suitable for most
applications. It is applied in this basic start-up procedure. Note however that this requires
that:
• parameter
is set to 1 (
VECTOR
:
SPEED
) or 2 (
VECTOR
:
TORQ
), or
• parameter
SCALAR
:
FREQ
) and parameter
is set to 3 (
SCALAR
FLYST
)
or 5 (
FLY
+
BOOST
).
If your selection is 0 (
OFF
/
IDMAGN
), move to the next step.
Value 1 (
ON
), which performs a separate ID Run, should be selected if:
• vector control mode is used [parameter
= 1 (
VECTOR
:
SPEED
) or 2 (
VECTOR
:
TORQ
)],
and/or
• the operation point is near zero speed, and/or
• operation at torque range above the motor nominal torque over a wide speed range and
without any measured speed feedback is required.
If you decide to do the ID Run [value 1 (
ON
)], continue by following the separate instructions
given on page
and then return to step
IDENTIFICATION MAGNETIZATION WITH ID RUN SELECTION 0 (OFF/IDMAGN)
As stated above, the identification magnetization is performed only if:
• parameter
is set to 1 (
VECTOR
:
SPEED
) or 2 (
VECTOR
:
TORQ
), or
• parameter
is set to 3 (
SCALAR
:
FREQ
) and parameter
is set to 3 (
SCALAR FLYST
)
or 5 (
FLY
+
BOOST
).
Press key
to switch to local control (LOC shown on the left).
Press
to start the drive. The motor model is now calculated by magnetizing the motor
for 10 to 15 s at zero speed (motor not rotating).
DIRECTION OF THE MOTOR ROTATION
Check the direction of the motor rotation.
• If the drive is in remote control (REM shown on the left),
switch to local control by pressing
.
• To go to the Main menu, press
if the bottom line shows
OUTPUT; otherwise press
repeatedly until you see
MENU at the bottom.
• Press keys
/
until you see “rEF” and press
.
• Increase the frequency reference from zero to a small value
with key
.
• Press
to start the motor.
• Check that the actual direction of the motor is the same as
indicated on the display (FWD means forward and REV
reverse).
• Press
to stop the motor.
LOC
REM
LOC
REM
LOC
Hz
SET
FWD
xxx
.
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...