ACS550 User’s Manual
77
Application macros
PID Control macro
This macro provides parameter settings for closed-loop control systems such as
pressure control, flow control, etc. To enable, set the value of parameter 9902 to
6 (
PID
CONTROL
).
Note:
Parameter 2108
START
INHIBIT
must remain in the default setting, 0 (
OFF
).
Connection example:
Input signals
Output signals
Jumper setting
• Analog reference (AI1)
• Actual value (AI2)
• Start/stop – hand/PID (DI1, 6)
• EXT1/EXT2 selection (DI2)
• Constant speed selection (DI3, 4)
• Run enable (DI5)
• Analog output AO1: Speed
• Analog output AO2: Current
• Relay output 1: Ready
• Relay output 2: Running
• Relay output 3: Fault (-1)
or
Note:
Use the following switch-on order:
1. EXT1/EXT2
2. Run Enable
3. Start.
1 SCR
2 AI1
3 AGND
4 10V
5 AI2
6 AGND
7 AO1
8 AO2
9 AGND
10 24V
11 GND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B
Start/Stop (Hand):
Activation starts the drive
Constant speed selection 1:
(Not used in PID control)
2
EXT1/EXT2 selection:
Activation selects PID control
Constant speed selection 2:
(Not used in PID control)
2
Start/Stop (PID):
Activation starts the drive
Run enable:
Deactivation always stops the drive
External ref. 1 (Manual) or Ext ref. 2 (PID):
0
…
10 V
1
Reference voltage 10 V DC
Motor output speed:
0
…
20 mA
Output current:
0
…
20 mA
Analog input circuit common
Analog output circuit common
Auxiliary voltage 24 V DC
Auxiliary voltage output common
Digital input common for all
Signal cable shield (screen)
Analog input circuit common
Relay output 1, programmable
Default operation:
Relay output 2, programmable
Default operation:
Relay output 3, programmable
Default operation:
Ready
=>19 connected to 21
Running
=>22 connected to 24
Fault (-1)
=>25 connected to 27
Note 2.
Code:
0 = open, 1 = connected
DI3 DI4
Output
0
0
Reference through AI1
1
0
CONST
SPEED
1 (1202)
0
1
CONST
SPEED
2 (1203)
1
1
CONST
SPEED
3 (1204)
Note 1.
Manual: 0
…
10V => speed reference
PID: 0
…
10V => 0
…
100% PID
setpoint
(Fault => 25 connected to 26)
Note 3.
The sensor needs to be powered.
See the manufacturer’s instructions.
A connection example of a two-wire
3
X1
1…10 kohm
Actual signal (PID):
4
…
20 mA
J1
AI1: 0
…
10 V
AI2: 0(4)
…
20 mA
ON
ON
AI1: 0
…
10 V
AI2: 0(4)
…
20 mA
ON
12
J1
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...