ACS550 User’s Manual
193
Embedded fieldbus
Activate drive control functions – EFB
Controlling the drive
Fieldbus control of various drive functions requires configuration to:
• tell the drive to accept fieldbus control of the function
• define as a fieldbus input, any drive data required for control
• define as a fieldbus output, any control data required by the drive.
The following sections describe, at a general level, the configuration required for
each control function. For the protocol-specific details, see the document supplied
with the FBA module.
Start/Stop Direction control
Using the fieldbus for start/stop/direction control of the drive requires:
• drive parameter values set as defined below
• fieldbus controller supplied command(s) in the appropriate location. (The location
is defined by the Protocol Reference, which is protocol dependent.)
Drive parameter
Value
Description
Modbus
1
protocol reference
ABB
DRV
DCU
PROFILE
1001
EXT
1
COMMANDS
10 (
COMM
)
Start/Stop by fieldbus
with Ext1 selected.
40001 bits 0…3 40031 bits 0, 1
1002
EXT
2
COMMANDS
10 (
COMM
)
Start/Stop by fieldbus
with Ext2 selected.
40001 bits 0…3 40031 bits 0, 1
1003
DIRECTION
3 (
REQUEST
) Direction by fieldbus.
4002/4003
2
40031 bit 3
1
For Modbus, the protocol reference can depend on the profile used, hence two columns in these
tables. One column refers to the ABB Drives profile, selected when parameter 5305 = 0 (
ABB
DRV
LIM
) or 5305 = 2 (
ABB
DRV
FULL
). The other column refers to the DCU profile selected when
parameter 5305 = 1 (
DCU
PROFILE
ABB control profiles technical data
on page
.
2
The reference provides direction control – a negative reference provides reverse rotation.
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...