54 Parameters
T20-4
20 to 4mA Signal, the
DRIVE
will trip and show the fault code
F0007
if the signal level falls below 3mA
r20-4
20 to 4mA Signal, the
DRIVE
will ramp to stop if the signal
level falls below 3mA
U10-0
10 to 0 Volt Signal (Uni-polar).The drive will operate at
maximum frequency/speed if the analog reference after
scaling and offset are applied is =<0.0%.
1301
ANALOG INPUT 1
OFFSET
Sets an offset, as a percentage of the full scale range of the
input, which is applied to the analog input signal
0.0%
-500…500 %
Value in percent of the full scale range of the input
Example: If the analog input signal format is 0-10V, offset =
20% .
An analog input signal level of 7 Volts gives the following
result :
Analog input level (%) = 7/10 = 70%
Result = 70-20 (%) = 50%
1302
ANALOG INPUT 1
SCALING
Scales the analog input by this factor, (as a percentage of the
full scale range of this input).
100.0
0.0…2000.0 %
Example: If parameter
1300
ANALOG INPUT 1 FORMAT is
set for 0 – 10V, and the scaling factor is set to 200.0%, a 5
volt input will result in the drive running at maximum speed as
set in parameter
2008
MAX SPEED LIMIT
1304
ANALOG INPUT 2
SIGNAL FORMAT
Selects the type of reference source into terminal 4.
U0-10
U0-10
0 to 10 Volt Signal
A0-20
0 to 20mA Signal
t4-20
4 to 20mA Signal, the
DRIVE
will trip and show the fault code
F0007
if the signal level falls below 3mA
r4-20
4 to 20mA Signal, the
DRIVE
will ramp to stop if the signal
level falls below 3mA
t20-4
20 to 4mA Signal, the
DRIVE
will trip and show the fault code
F0007
if the signal level falls below 3mA
r20-4
20 to 4mA Signal, the
DRIVE
will ramp to stop if the signal
level falls below 3mA
ptc-th
Use for motor thermistor
14
RELAY OUTPUTS
Status information indicated through relay output and relay
operating delays
1401
OUTPUT RELAY
FUNCTION
SELECT
Selects the function assigned to the relay output. The relay
has two output terminals, Logic 1 indicates the relay is active,
and therefore terminals 10 and 11 will be linked together.
1
0 : DRIVE
ENABLED
(RUNNING)
Logic 1 when the motor is enabled
1 : DRIVE READY
Logic 1 when power is applied to the drive and no fault exists
2 : AT TARGET
FREQUENCY
(SPEED)
Logic 1 when the output frequency matches the setpoint
frequency
3: DRIVE TRIPPED
Logic 1 when the drive is in a fault condition
4 : OUTPUT
FREQUENCY >=
LIMIT
Logic 1 when the output frequency exceeds the adjustable
limit set in
3200
RELAY THRESHOLD LEVEL
ACS260-04.book Page 54 Thursday, December 24, 2020 4:33 PM
Summary of Contents for ACS260-04 Series
Page 2: ...ACS260 04 book Page 2 Thursday December 24 2020 4 33 PM ...
Page 4: ...ACS260 04 book Page 4 Thursday December 24 2020 4 33 PM ...
Page 8: ...8 Table of contents ACS260 04 book Page 8 Thursday December 24 2020 4 33 PM ...
Page 14: ...14 Safety ACS260 04 book Page 14 Thursday December 24 2020 4 33 PM ...
Page 22: ...22 Mechanical installation ACS260 04 book Page 22 Thursday December 24 2020 4 33 PM ...
Page 32: ...32 Electrical installation ACS260 04 book Page 32 Thursday December 24 2020 4 33 PM ...
Page 92: ...92 Technical Data ACS260 04 book Page 92 Thursday December 24 2020 4 33 PM ...
Page 96: ...96 Options and Kits ACS260 04 book Page 96 Thursday December 24 2020 4 33 PM ...