Fault tracing 73
F0002
0x06
Over voltage on DC bus
Check the supply voltage is within the allowed
tolerance for the drive. If the fault occurs on
deceleration or stopping, increase the deceleration
time in parameter
2203
or install a suitable brake
resistor and activate the dynamic braking function
with parameter
2020
F0006
0x07
Under voltage on DC bus
The incoming supply voltage is too low. This trip
occurs routinely when power is removed from the
drive. If it occurs during running, check the incoming
power supply voltage and all components in the
power feed line to the drive.
F0003
0x08
Heatsink over temperature
The drive is too hot. Check the ambient temperature
around the drive is within the drive specification.
Ensure sufficient cooling air is free to circulate
around the drive.
Increase the panel ventilation if required. Ensure
sufficient cooling air can enter the drive, and that the
bottom entry and top exit vents are not blocked or
obstructed.
U-t
0x09
Under temperature
Trip occurs when ambient temperature is less than -
10°C. The temperature must be raised over -10°C in
order to start the drive.
F0018
0x10
Faulty thermistor on
heatsink.
Refer to your local ABB representative
O-hEAt
0x17
Drive internal temperature
too high
Drive ambient temperature too high, check adequate
cooling air is provided
F0014
0x0B
External trip
(on digital input 3)
E-trip requested on control input terminals. Some
settings of parameter
9902
DIGITAL INPUTS
FUNCTION SELECT require a normally closed
contactor to provide an external means of tripping the
drive in the event that an external device develops a
fault. If a motor thermistor is connected check if the
motor is too hot.
F0010
0x0C
Comms loss trip
Check communication link between drive and
external devices. Make sure each drive in the
network has its unique address.
F0022
0x0E
Input phase loss trip
Drive intended for use with a 3 phase supply has lost
one input phase.
SPIn-F
0x0F
Spin start failed
Spin start function failed to detect the motor speed.
F0027
0x11
Internal memory fault.
Parameters not saved, defaults reloaded.
Try again. If problem recurs, refer to your local ABB
representative
F0007
0x12
Analog input current out of
range
Check input current in range defined by parameter
1300
.
F0021
-
Internal drive Fault
Refer to your local ABB representative
fauLty
-
Internal drive Fault
Refer to your local ABB representative
Fault
Code
No.
Description
Corrective Action
ACS260-04.book Page 73 Thursday, December 24, 2020 4:33 PM
Summary of Contents for ACS260-04 Series
Page 2: ...ACS260 04 book Page 2 Thursday December 24 2020 4 33 PM ...
Page 4: ...ACS260 04 book Page 4 Thursday December 24 2020 4 33 PM ...
Page 8: ...8 Table of contents ACS260 04 book Page 8 Thursday December 24 2020 4 33 PM ...
Page 14: ...14 Safety ACS260 04 book Page 14 Thursday December 24 2020 4 33 PM ...
Page 22: ...22 Mechanical installation ACS260 04 book Page 22 Thursday December 24 2020 4 33 PM ...
Page 32: ...32 Electrical installation ACS260 04 book Page 32 Thursday December 24 2020 4 33 PM ...
Page 92: ...92 Technical Data ACS260 04 book Page 92 Thursday December 24 2020 4 33 PM ...
Page 96: ...96 Options and Kits ACS260 04 book Page 96 Thursday December 24 2020 4 33 PM ...