68 Parameters
Keypad Mode: (
1103 = 1 or 2)
Notes (keypad mode):
1. When changing from other speed reference (e.g. preset speed or analog speed)
back to keypad speed reference (digital pot value) while drive is running, the
following behaviour will be expected:
If
1100
= 0 or 2, digital pot speed value will be set to minimum speed
2007
to start
with.
If
1100
= 1 or 3, digital pot will keep unchanged from last time adjustment.
If
1100
= 4 or 6, digital pot value will be updated to be the same as current motor
running speed.
If
1100
= 5 or 7, digital pot value will be set to the same value as preset speed 4 to
start with.
2. When drive is not running:
If
1100
= 0, 2, 4 or 6, digital pot speed value will be set to minimum speed
2007
.
If
1100
= 1 or 3, digital pot will keep unchanged.
9902
Digital input 1
Digital input 2
Digital input 3 (An
In 2)
Analog input
Comments
0,
8...13
Open: Stop
(disable)
Closed: Run
(enable)
Closed: remote
UP push-button
Closed: remote
DOWN push-button
Open: Forward
Closed: Reverse
1
Open: Stop
(disable)
Closed: Run
(enable)
No effect
No effect
No effect
Default speed
reference is PI
controller speed
reference
2
Open: Stop
(disable)
Closed: Run
(enable)
Closed: remote
UP push-button
Closed: remote
DOWN push-button
Open: Keypad
speed ref
Closed: Preset
speed 1
3
Open: Stop
(disable)
Closed: Run
(enable)
Closed: remote
UP push-button
External
trip/thermistor input:
Open: Trip, Closed:
Run
Closed: remote
DOWN push-
button
Connect external
thermistor type
PT100 or similar to
digital input 3
4
Open: Stop
(disable)
Closed: Run
(enable)
Closed: remote
UP push-button
Open: Keypad
speed ref
Closed: Analog
input 1
Analog input 1
5
Open: Stop
(disable)
Closed: Run
(enable)
Open: Forward
run
Closed: reverse
run
Open: Keypad
speed ref
Closed: Analog
input 1
Analog input 1
6
Open: Stop
(disable)
Closed: Run
(enable)
Open: Forward
run
Closed: reverse
run
External
trip/thermistor input:
Open: Trip, Closed:
Run
Open: Keypad
speed ref
Closed: Preset
speed 1
Connect Ext
thermistor type
PT100 or similar to
Digi input 3
7
Open: Fwd Stop
Closed: Fwd
Run
Open: reverse
Stop
Closed: reverse
Run
External
trip/thermistor input:
Open: Trip, Closed:
Run
Open: Keypad
speed ref
Closed: Preset
speed 1
Closing digital
inputs 1 and 2
together carries
out a fast stop
14
Open: Stop
(disable)
Closed: Run
(enable)
No effect
External
trip/thermistor input:
Open: Trip, Closed:
Run
No effect
Connect external
thermistor type
PT100 or similar to
digital input 3
ACS260-04.book Page 68 Thursday, December 24, 2020 4:33 PM
Summary of Contents for ACS260-04 Series
Page 2: ...ACS260 04 book Page 2 Thursday December 24 2020 4 33 PM ...
Page 4: ...ACS260 04 book Page 4 Thursday December 24 2020 4 33 PM ...
Page 8: ...8 Table of contents ACS260 04 book Page 8 Thursday December 24 2020 4 33 PM ...
Page 14: ...14 Safety ACS260 04 book Page 14 Thursday December 24 2020 4 33 PM ...
Page 22: ...22 Mechanical installation ACS260 04 book Page 22 Thursday December 24 2020 4 33 PM ...
Page 32: ...32 Electrical installation ACS260 04 book Page 32 Thursday December 24 2020 4 33 PM ...
Page 92: ...92 Technical Data ACS260 04 book Page 92 Thursday December 24 2020 4 33 PM ...
Page 96: ...96 Options and Kits ACS260 04 book Page 96 Thursday December 24 2020 4 33 PM ...