60 Parameters
2606
EFFECTIVE
SWITCHING
FREQUENCY
Sets maximum effective switching frequency of the
drive. If “rEd” is displayed, the switching frequency
has been reduced to the level in Parameter
0417
INTERNAL EFFECTIVE SWITCHING FREQUENCY
due to excessive drive heat sink temperature.
Refer to parameter
0417
INTERNAL EFFECTIVE
SWITCHING FREQUENCY for further information
regarding operation at higher switching frequency.
Drive Rating
Dependent
4…32 kHz
2610
V/F
CHARACTERISTIC
ADJUSTMENT
VOLTAGE
Used in conjunction with parameter
2611
V/F
CHARACTERISTIC ADJUSTMENT FREQUENCY
0 V
0 V…250/500
2611
V/F
CHARACTERISTIC
ADJUSTMENT
FREQUENCY
This parameter in conjunction with parameter
2610
V/F CHARACTERISTIC ADJUSTMENT VOLTAGE
sets a frequency point at which the voltage set in
parameter
2611
V/F CHARACTERISTIC
ADJUSTMENT FREQUENCY is applied to the motor.
Care must be taken to avoid overheating and
damaging the motor when using this feature.
0.0 Hz
0.0 Hz…Value set in
9907
30 FAULT FUNCTIONS
Programmable protection functions
3005
THERMAL
OVERLOAD VALUE
RETENTION
0 : DISABLED
0 : DISABLED
Alternative means of protecting the motor from
thermal overload must be applied (e.g. PTC
thermistor)
1 : ENABLED
The drive will retain the motor thermal overload value
following a mains power cycle.
THERMAL
OVERLOAD
MANAGEMENT
0 : DISABLED
1 : ENABLED
32 SUPERVISION
Signal supervision. The drive monitors whether
certain user selectable variables are within the user-
defined limits. The user may set limits for speed,
current etc. Supervision status can be monitored with
relay output. See parameter group 14 RELAY
OUTPUTS.
3200
RELAY
THRESHOLD
LEVEL
Adjustable threshold level used in conjunction with
settings 4 to 7 of parameter
1401
OUTPUT RELAY
FUNCTION SELECT
100.0 %
0.0…200.0 %
34 PANEL DISPLAY
Selection of actual signals to be displayed on the
drives front panel e.g. to display conveyer speed in
meters per second based on the output frequency
3400
DISPLAY
SCALING
FACTOR
Allow the user to display an alternative output unit
scaled from an existing parameter, This function is
disabled if set to 0.000.
0.000
ACS260-04.book Page 60 Thursday, December 24, 2020 4:33 PM
Summary of Contents for ACS260-04 Series
Page 2: ...ACS260 04 book Page 2 Thursday December 24 2020 4 33 PM ...
Page 4: ...ACS260 04 book Page 4 Thursday December 24 2020 4 33 PM ...
Page 8: ...8 Table of contents ACS260 04 book Page 8 Thursday December 24 2020 4 33 PM ...
Page 14: ...14 Safety ACS260 04 book Page 14 Thursday December 24 2020 4 33 PM ...
Page 22: ...22 Mechanical installation ACS260 04 book Page 22 Thursday December 24 2020 4 33 PM ...
Page 32: ...32 Electrical installation ACS260 04 book Page 32 Thursday December 24 2020 4 33 PM ...
Page 92: ...92 Technical Data ACS260 04 book Page 92 Thursday December 24 2020 4 33 PM ...
Page 96: ...96 Options and Kits ACS260 04 book Page 96 Thursday December 24 2020 4 33 PM ...