Parameters 53
2: BI-DIRECTIONAL
KEYPAD CONTROL.
The drive can be controlled in the forward and reverse
directions using an external or remote Keypad. Pressing
the keypad START button toggles between forward and
reverse.
3: MODBUS NETWORK
CONTROL.
Control via Modbus RTU (RS485) using the internal accel
/ decel ramps
4 : MODBUS NETWORK
CONTROL.
Control via Modbus RTU (RS485) interface with accel /
decel ramps updated via Modbus
5 : PI CONTROL
User PI control with external feedback signal
6 : PI ANALOG
SUMMATION CONTROL.
PI control with external feedback signal and summation
with analog input 1
12
CONSTANT
SPEEDS
Constant speeds. Constant speed activation overrides the
external speed reference. Constant speed selections are
ignored if the drive is in the local control mode.
Preset Speeds / Frequencies selected by digital inputs
depending on the setting of Parameter
9902
DIGITAL
INPUTS FUNCTION SELECT.
If Parameter
9908
MOTOR RATED SPEED = 0, the values
are entered as Hz. If Parameter
9908
> 0, the values are
entered as Rpm.
Setting a negative value will reverse the direction of motor
rotation.
1202
PRESET / JOG
FREQUENCY /
SPEED 1
Defines constant speed 1 (that is the drive output frequency)
6.0
Hz/RPM
2007…
-
2008
Output Frequency
1203
PRESET / JOG
FREQUENCY /
SPEED 2
Defines constant speed 2 (that is the drive output frequency)
12.0
Hz/RPM
2007…
-
2008
Output Frequency
1204
PRESET / JOG
FREQUENCY /
SPEED 3
Defines constant speed 3 (that is the drive output frequency)
18.0
Hz/RPM
2007…
-
2008
Output Frequency
1205
PRESET / JOG
FREQUENCY /
SPEED 4
Defines constant speed 4 (that is the drive output frequency)
24.0
Hz/RPM
2007…
-
2008
Output Frequency
13
ANALOG INPUTS
1300
ANALOG INPUT 1
SIGNAL FORMAT
Selects the type of reference source into terminal 6.
U 0-10
U0-10
0 to 10 Volt Signal(Uni-polar).The drive will remain at 0.0Hz
if the analog reference after scaling and offset are applied is
<0.0%.
B-10-10
0 to 10 Volt Signal (Bi-polar). The drive will operate the
motor in the reverse direction of rotation if the analog
reference after scaling and offset are applied is <0.0%
A0-20
0 to 20mA Signal
T4-20
4 to 20mA Signal, the
DRIVE
will trip and show the fault
code
F0007
if the signal level falls below 3mA
R4-20
4 to 20mA Signal, the
DRIVE
will ramp to stop if the signal
level falls below 3mA
ACS260-04.book Page 53 Thursday, December 24, 2020 4:33 PM
Summary of Contents for ACS260-04 Series
Page 2: ...ACS260 04 book Page 2 Thursday December 24 2020 4 33 PM ...
Page 4: ...ACS260 04 book Page 4 Thursday December 24 2020 4 33 PM ...
Page 8: ...8 Table of contents ACS260 04 book Page 8 Thursday December 24 2020 4 33 PM ...
Page 14: ...14 Safety ACS260 04 book Page 14 Thursday December 24 2020 4 33 PM ...
Page 22: ...22 Mechanical installation ACS260 04 book Page 22 Thursday December 24 2020 4 33 PM ...
Page 32: ...32 Electrical installation ACS260 04 book Page 32 Thursday December 24 2020 4 33 PM ...
Page 92: ...92 Technical Data ACS260 04 book Page 92 Thursday December 24 2020 4 33 PM ...
Page 96: ...96 Options and Kits ACS260 04 book Page 96 Thursday December 24 2020 4 33 PM ...