64 / 128
Identification: MD-AL-GI-00
Rev. 1.0 of 21/07/2021 - Application: GID
User’s Manual 1PH 3000TLM-6000TLM-V3
Rev. 1.0 21/07/2021
ID55
Reserved
Reserved
ID57
TempFault_Env1
environment
temperature1 protection
ID58
Reserved
Reserved
ID59
TempFault_Inv1
Model 1 over-temperature
protection
ID60
Reserved
Reserved
ID61
Reserved
Reserved
ID65
VbusRmsUnbalance
Unbalanced RMS value of
bus voltage
There are internal faults of
inverter, turn OFF the “DC
switch”, wait for 5 minutes, then
turn ON the “DC switch”. Check
whether the fault is rectified. If
no, please contact technical
support.
ID66
VbusInstantUnbalance
Unbalanced instantaneous
value of bus voltage
ID67
BusUVP
Bus undervoltage during
grid connection
If the configuration of the PV
array is correct, could be the sun
irradiation is too low. Once sun
irradiation back to normal,
inverter will work back normal.
ID68
BusZVP
Bus voltage is low
There are internal faults of
inverter, turn OFF the “DC
switch”, wait for 5 minutes, then
turn ON the “DC switch”. Check
whether the fault is rectified. If
no, please contact technical
support.
ID69
PVOVP
PV overvoltage