User’s Manual 1PH 3000TLM-6000TLM-V3
Rev. 1.0 21/07/2021
Cable connection procedure
1)
Identify the suitable cables as shown in table 2 and remove an appropriate length of the protective
sheath, as shown in the figure (A: 30~50 mm B: 6~8 m).
Figure 18 - Connecting the AC output cables (1)
2)
Disassemble the AC connector as shown in the figure below; insert the AC output cable (with its stripped
insulation layer as shown in step 1) through the PG waterproof cable gland.
Figure 19 - Connecting the AC output cables (2)
3)
Connect the AC power cable according to the following criteria:
• Connect the ground wire (yellow-green) to the hole labelled “PE”, and tighten the cable with an Allen
key;
• Connect the line wire (brown) to the hole labelled “L”, and tighten the cable with an Allen key;
• Connect the neutral wire (blue) to the hole labelled “N”, and tighten the cable with an Allen key;