53 / 128
Identification: MD-AL-GI-00
Rev. 1.0 of 21/07/2021 - Application: GID
User’s Manual 1PH 3000TLM-6000TLM-V3
Rev. 1.0 21/07/2021
On-Off Control
Inverter on-off local control.
Set Energy
Set the total power generation. You can modify the total power generation through this option.
Set address
Set the address (when you need to monitor multiple inverters simultaneously). Default 01.
The Address indicates the address used by the inverter to send its data to the monitoring server. Address 01
is used for single inverters; to extend the monitoring to multiple inverters, use progressive communication
addresses.
Note: make sure that the address entered is never 00, because this setting would exclude the possibility of
communication between the inverter and the Wi-Fi network or RS485 port.
Set Input mode
1PH 3000TLM-6000TLM-V3 has 2 MPPT circuit, each MPPT circuit can work interdependently, or divided
into parallel mode. User can change the setting according to the configuration.
Set Language
Set the inverter display language.
Set Reflux P
Enable or disable the anti-reflux function of the inverter, and set the reflux power. This function need to be
used with external CT.
EnDRMs
Enable or disable logical interfaces.
IV Curve Scan
Shadow scanning, when the component is blocked or abnormal, causing multiple power peaks, by
enabling this function, the peak point of maximum power can be tracked.
Autotest Fast