TMD-Display One
Technical Support:
http://zennioenglish.zendesk.com
66
Time of day
: represents the current time (“hh:mm” in 24-hour format). Note
that the time of day must be set through the bus by an external reference. In
addition, in the absence of power the clock will get outdated.
Text from object
: represents a string (up to 14 characters) received through
the corresponding communication object.
[Climate] Temp
: represents temperature values as received through the
related communication object. Values in the range [-99, 199] ºC are available.
Values out of range will be replaced by the corresponding limit.
When the value contains decimals, only the first one will be shown, and it will
be represented in a smaller size. Also, if the decimal part does not fit, the
number will be rounded to the nearest integer.
[Climate] Mode
: represents climate modes as received through the
associated communication object. There are two Mode Types:
Heat/Cool: only the Heat and Cool modes will be represented, according to
the value of a one-bit object.
Extended: up to five HVAC climate modes will be represented, according
to the value received through a specific one-byte object. The icons are
represented with a progressive shift in the box, i.e., the first mode is shown
at the left and the last at the right.
If the object value does not correspond to a valid mode, no icon will be
displayed.
[Climate] Fan
: represents fan speeds, according to the value of the
corresponding object. There are up to 4 fan speed levels: Off/Auto, Min, Med,
Max. The number of levels can be customised, as explained later.
As with climate modes, the icons of the successive levels are represented
with a progressive shift, but without hiding the preceding ones.
[Climate] On/Off + Mode + Status
: climate status indicator with three one-bit
objects associated: On/Off, Mode and Status. The icon represented depends
on the value of these three objects, as explained in next section.