KLIC-LG1
http://www.zennio.com
Technical Support:
http://support.zennio.com
24
81-100%
100%
Position 5
Table 4. Flap position (five positions).
o
“Six positions”:
Control Values
Status Value
Position Sent to the Unit
1-16%
16%
Position 1
17-33%
33%
Position 2
34-50%
50%
Position 3
51-66%
66%
Position 4
67%-83%
83%
Position 5
84%-100%
100%
Position 6
Table 5. Flap position (six positions).
Swing Object Polarity
: sets the polarity of the enabled
object: “0 = Swing
Off; 1 = Swing On
” or “0 = Swing On; 1 = Swing Off”.
Swirl available
: sets whether the A/C unit incorporates a Swirl function.
If enabled, the "
[AC]
Horizontal Flaps: Swirl
"
and "
[AC]
Horizontal
Flaps: Swirl (Status)
" binary objects are incorporated into the project
topology to allow activating or deactivating such mode and consulting
whether it is currently active, respectively.
Vertical Flaps
:
enables the “
[AC] Vertical Flaps: Swing
” and “
[AC] Vertical
Flaps: Swing (Status)
” 1-Bit objects, which will let activating/deactivating the
swing function or reading its current status, respectively.
Swing Object Polarity
: sets the polarity of the enabled
object: “0 = Swing
Off; 1 = Swing On
” or “0 = Swing On; 1 = Swing Off”.
2.4.4
INITIAL CONFIGURATION
The custom initial configuration allows setting the desired status that KLIC-LG1 will send
the A/C unit after downloading or restarting the device. This status is defined in terms of
on/off, mode, fan speed, flaps position and temperature setpoint.
In addition, it is possible to activate an initial sending of this status to the KNX bus.