ETS PARAMETRISATION
After enabling this function, the menu on the left will show a new tab named Flaps,
containing the following parameters:
Figure 16: A/C Gateway. Flaps.
Horizontal Flaps
:
enables the “
[AC] Horizontal Flaps: Swing
” and “
[AC]
Horizontal Flaps: Swing (Status)
” 1-Bit objects, which will let
activating/deactivating the swing function or reading its current status,
respectively.
Direct Positioning
: enables the "
[AC]
Horizontal Flaps: Percentage
Control
” 1-byte object, which allow setting the position of the flaps.
Number of Flap Positions
:
either “5” or “6”. This determines the values
of the
"[AC]
Horizontal Flaps: Percentage Control
”
object. The
following tables show the percentage values that correspond to each of
the available positions:
o
“Five positions”:
Control Values
Status Value
Position Sent to the Unit
1-20%
20%
Position 1
21-40%
40%
Position 2
41-60%
60%
Position 3
61-80%
80%
Position 4