![Zennio KLIC-LG1 Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/zennio/klic-lg1/klic-lg1_user-manual_3405418019.webp)
KLIC-LG1
http://www.zennio.com
Technical Support:
http://support.zennio.com
19
OPERATING TIME
The hours that A/C unit has been operating can be known through the 2-byte object
“[AC] Operating time”
. This object can be read and overwritten during run time.
Furthermore, the available parameters in ETS are:
Initial Operation Time
:
“Keep current value”: option enabled by default, which keep the previous
value.
“Set value”: allows establishing an initial operating time value.
Periodic Sending
: resending period (in hours) of operating time If set to 0 the
periodic send is disabled.
When operating time object reaches its maximum value (65535 hours), it will be send
through KNX bus (in spite of the fact that the periodical sending has not been configured)
and it will keep this value until the user reset it.
AUTOMATIC OFF
Figure 12: A/C Gateway. Configuration. Automatic Off.
Automatic Off
:
enables the “
[AC] Automatic Off
” and the
“[AC] Automatic
Off (Status)”
binary objects, which lets performing a temporary switch-off of
Figure 1. A/C Gateway. Configuration. Operating time.