later sections of this document. Please, note that
AC Gateway
is permanently
enabled.
Heartbeat (Periodical Alive Notification)
: this parameter lets the integrator
incorporate a 1-B
it object to the project (“
[Heartbeat] Object to Send ‘1’
”) that
will be sent periodically with value “1” to notify that the device is still working
(
still alive
).
Figure 4. Heartbeat.
Note
:
The first sending after download or bus failure takes place with a delay
of up to 255 seconds, to prevent bus overload. The following sendings match
the period set
.
Regardless of the above parameters, the following objects are available by default:
“
[AC] On/Off
” and “
[AC] On/Off (Status)
”: allow switching on (value “1”) and
off (value “0”) the A/C unit or reading the current status, respectively.
“
[AC] Temperature Setpoint
” and “
[AC] Temperature Setpoint (Status)
”:
allow setting the desired temperature setpoint or reading the current value,
respectively. See section 2.4.1 for further options.
“
[AC] Mode
” and “
[AC] Mode (Status)
”: allow setting the desired operation
mode (either Automatic, Heating, Cooling, Fan or Dry) or reading the current
mode, respectively. See section 2.4.1 for further options.
“[AC] Speed: Percentage Control”
and
“[AC] Speed Percentage control
(Status)”:
allow setting the desired speed or reading the current speed,
respectively. See section 2.4.1 for further options.
“[AC] Operating Time”:
shows the time in hours that the A/C unit has been
working. See section 2.4.1 for further options.