30 / 45
6.
Communication Addr.
Select “6. Set Communication Addr.”, press “OK”. Press “Up” or “Down” to change the 1
st
digit, press “OK” to switch
to next digit, after changing the 485-communication address (
default :01
), press “OK”.
7.
Auto Test (ONLY for Italian Market)
Select “7. Auto Test”, press “OK” to enter autotest interface.
7.Auto Test
1.Autotest Fast
2.Autotest STD
3.QF Time Setting
4.QV Time Setting
5.Control 81.S1
1)
Autotest Fast
Select “1. Autotest Fast”, then press “OK” to start Auto test Fast.
Start Autotest
↓
Press “Ok” to start
Testing 59.S1...
↓
Wait
Test 59.S1 OK!
↓
Wait
Testing 59.S2...
↓
Wait
Test 59.S2 OK!
↓
Wait
Testing 27.S1...
↓
Wait
Test 27.S1 OK!
↓
Wait
Testing 27.S2...
↓
Wait
Test 27.S2 OK!
↓
Wait
Testing 81>S1...
↓
Wait
Test 81>S1 OK!
↓
Wait
Testing 81>S2…
↓
Wait
Test 81>S2 OK!
↓
Wait
“Up”
↑
“Down”
↓