33 / 45
1.
Battery Parameter
1.Battery Parameter
1)Battery Type
7)Max Discharge (A)
2)*Battery Capacity
8)*Low (V) Protection
3)Discharge Depth
9)*Min Discharge (V)
4)Max Charge (A)
10)*Empty Discharged (V)
5)*Over (V) Protection
11)*Full Charged (V)
6)*Max Charge (V)
12)Save
Note: 2)*, 5)*, 6)*, 8)*, 9)*, 10)* and 11)* settings are only if DEFAULT battery type was selected.
1)
Battery Type (refer to Set
Select “1. Battery Type” and press “OK”. Press “up” or “down” to select the battery type. Press “OK” to confirm.
2)
*Battery Capacity (only for DEFAULT battery type)
Select “2. Battery Capacity” and press “OK”. Press “up” or “down” to change the 1
st
digit, press “ok” to confirm the
value and move to next digit. Input the value of battery capacity. Press “OK”.
3)
Discharge Depth
Select “3. Discharge Depth” and press “OK” to enter discharge depth interface.
Discharge Depth
50%
EPS Discharge Depth
80%
EPS Restore Depth
20%
Press “up” or “down” to change the 1
st
digit, press “ok” to confirm the value and move to next digit. Input the
Discharge Depth & EPS Discharge Depth value per battery specification. Press “OK”.
For example: if Discharge Depth = 50% & EPS Discharge Depth = 80% while grid is present: HYD-ES inverter won’t
discharge the battery when its SOC is less than 50%, In case of blackout the HYD-ES inverter will work in EPS mode (if
EPS mode is enabled) & keep discharging the battery till battery SOC is less than 20%.
4)
Max. Charge (A)
Select “4. Max. Charge (A)” and press “OK”. Press “up” or “down” to change the 1
st
digit, press “ok” to confirm the
value and move to next digit. Input the value of Max. Charge (A) per battery specification. Press “OK”.
5)
*Over (V) Protection (only for DEFAULT battery type)