28 / 45
Note: normally this mode is used to test whether HYD-ES inverter
can charge & discharge correctly or not. So basically, this mode is
used for testing purposes only.
From the menu is possible to program:
At what time the inverter start to charge the battery from the grid
At what time the inverter should stop charging the battery.
At what time the inverter start to discharge the battery to the grid
At what time the inverter should stop discharging the battery.
At which power the battery should be charged.
At which power the battery should be discharged.
4)
Set Passive Mode
Select “4. Set Passive Mode”, and then press “OK”.
For more detailed information, please ask ZCS technical support to get a copy of passive mode communication
protocol.
4.
PV Input Mode
PV input mode selection: The HYD-ES inverter has 2 MPPT channels. The 2 MPPT can operate independently or in
parallel. If the PV strings are connected in parallel outside the inverter, you should choose the “parallel mode”,
otherwise use the default setting (independent mode).
Charge Start 22 h 00 m
Charge End 05 h 00 m
Charge Power 2000 W
DisCharge Start 14 h 00m
DisCharge End 16 h 00m
DisCharge Power 2500 W