FORM 201.24-NM2
89
YORK INTERNATIONAL
The cooler and condenser design al-
lows for an increase in pressure drop
of up to 15% above the design value
given. Debris in the water may also
cause additional pressure drop.
When using glycol solutions, pressure
drops are higher than with water. Spe-
cial care must be taken not to exceed
the maximum allowed.
Ethylene Glycol
Propylene Glycol
LCHLT °C
Concentration
Concentration
% w/w
% w/w
6
5
5
4
12
13
2
18
20
0
23
25
-2
28
30
-4
32
34
-6
35
38
TABLE 13 – RECOMMENDED GLYCOL SOLUTION
STRENGTHS
ETHYLENE GLYCOL
PROPYLENE GLYCOL
B
A
C
B
A
C
FIG. 24 – GLYCOL SOLUTION STRENGTHS
A = Correction Factor
B = Temperature
C = Concentration %
Through Cooler
LD06934