FORM 201.24-NM2
55
YORK INTERNATIONAL
4.6 OPERATING HRS / START COUNTER KEY
When the key is pressed, the accumulated running hours
and starts for refrigerant system 1 and 2 compressors
are displayed.
Display Limits: Maximum run hours 99,999
Maximum starts 99,999
Values roll over to zero, if the maximum limit is exceeded.
These counters are zeroed at the fac-
tory, but may indicate run time and
number of starts logged during fac-
tory testing before shipment.
4.7 OPTIONS KEY AND DIP SWITCH SETTINGS
This key provides a display of options which are pro-
grammed by the positions of the S1 Dip Switches on
the AMB board. Proper programming of the switches
is important during the commissioning of the chiller.
The options key can be used to verify the Dip Switch
positions without checking the AMB board.
Each press of the key will scroll to the next option/dip
switch setting.
Four Option Switch Messages (S1-1 to S1-4) will then
be displayed in sequence. At the end of the sequence,
the display will automatically revert to the first Option
Switch message.
The following is a detailed guide to programming the
Dip Switches together with the associated display mes-
sage provided for each selection when the ‘OPTIONS’
key is pressed:
SWITCH 1: Water / Brine Cooling
Open:
Water cooling mode is for water cooling applications
and allows the chilled liquid leaving temperature set-
point to be programmed from 4.4 to 21.1°C.
Selecting this mode also auto-programs the low chilled
liquid cutout at 2.2°C and the suction pressure cutout
at 3.03 bar.
Closed:
Brine cooling mode is for brine/glycol applications with
setpoints below 4.4°C and allows the chilled liquid leav-
ing temperature setpoint to be programmed from -
12.2 to 21.1°C.
In this mode, the low chilled liquid cutout can be pro-
grammed from -13.3 to 2.2°C and the suction pressure
cutout can be programmed from 0.34 to 4.83 bar.
SWITCH 2: Ambient Temp. Low Limit
Open:
Standard ambient mode with the low ambient cutout
set at -3.9°C (not adjustable).
Closed:
Low ambient mode allows the low ambient cutout to
be programmed from -17.8 to 10°C.
SWITCH 3: Refrigerant
Open:
The R-22 mode MUST be selected.
The closed position MUST NOT be se-
lected. Incorrect selection of this
switch may cause serious damage to
the chiller.
SWITCH 4: Unit
Open:
H R S
1 =
1 1 4 3 . 2
=
1 3 8 2
S T R
1 =
2 8 5 . 2
=
3 2 2
S 1 - 1
C H I L L E D
L I Q U I D
W A T E R
S 1 - 1
C H I L L E D
L I Q U I D
G L Y C O L
S 1 - 2
A M B I E N T
C O N T R O L
S T A N D A R D
S 1 - 2
A M B I E N T
C O N T R O L
L O W
A M B I E N T
S 1 - 3
R E F R I G E R A N T
R - 2 2
S 1 - 4
Y C W S
7
Содержание YCWS0313SC
Страница 12: ...YORK INTERNATIONAL 12 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT...
Страница 36: ...YORK INTERNATIONAL 36 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT Commissioning...
Страница 86: ...YORK INTERNATIONAL 86 TYPICAL CONTROL PANEL WIRING Maintenance...
Страница 87: ...FORM 201 24 NM2 87 YORK INTERNATIONAL TYPICAL CONTROL PANEL WIRING LD06957 8...
Страница 91: ...FORM 201 24 NM2 91 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT 9...
Страница 101: ...FORM 201 24 NM2 101 YORK INTERNATIONAL SECTION 10 SPARE PARTS This information will be available at a later date 10...
Страница 103: ...FORM 201 24 NM2 103 YORK INTERNATIONAL NOTES 11...