YORK INTERNATIONAL
56
YCWS mode MUST be selected. The
closed position MUST NOT be se-
lected. Incorrect selection of this
switch may cause serious damage to
the chiller.
4.8 DIP SWITCH SETTING
4.9 FUNCTION KEY
Pressing this key displays the same message as press-
ing the ‘STATUS’ key.
Pressing the ‘FUNCTION’ key followed by another
display key will scroll through all the data available
under the display key once.
For example, pressing the ‘FUNCTION’ key followed
by the ‘SYSTEM 1 DATA’ key will result in scrolling
through the displays shown below, without the need to
press the ‘SYSTEM 1 DATA’ key to scroll to the next
display.
After scrolling through the data, the display returns to
the status message.
The FUNCTION Key can be used to scroll through the
displays for:
• Chilled Liquid Temps
• System # Data
• Motor Current
• Options
FIG. 16 – ENLARGED PHOTOGRAPH OF DIP
SWITCHES ON MICROPROCESSOR
BOARD
LD03511A
LD03511B
“OPEN” Position:
Left side of switch
pushed in
“CLOSED” Position:
Right side of switch
pushed in
S Y S
#
O I L
=
1 . 1
B A R D
S P = 3 . 7 9
D P =
1 7 . 1
B A R G
S Y S
#
O I L
=
5 5 . 5
° C
S P = 3 . 7 9
D P
=
4 9 . 6
° C
S Y S
#
S A T S U C T =
- 4 . 3 ° C
S U C T
S
H E A T
=
1 0 . 4 ° C
S Y S #
S A T
D S C H =
5 4 . 4 ° C
S U C T
S
H E A T
=
1 2 . 5 ° C
S Y S #
S
V
S T E P = 3
S Y S #
C O O L E R
I N L E T
R E F R I G
T E M P
=
- 2 . 5 ° C
Micropanel
LD06630
Содержание YCWS0313SC
Страница 12: ...YORK INTERNATIONAL 12 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT...
Страница 36: ...YORK INTERNATIONAL 36 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT Commissioning...
Страница 86: ...YORK INTERNATIONAL 86 TYPICAL CONTROL PANEL WIRING Maintenance...
Страница 87: ...FORM 201 24 NM2 87 YORK INTERNATIONAL TYPICAL CONTROL PANEL WIRING LD06957 8...
Страница 91: ...FORM 201 24 NM2 91 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT 9...
Страница 101: ...FORM 201 24 NM2 101 YORK INTERNATIONAL SECTION 10 SPARE PARTS This information will be available at a later date 10...
Страница 103: ...FORM 201 24 NM2 103 YORK INTERNATIONAL NOTES 11...