
YORK INTERNATIONAL
76
this point, the chiller will shutdown. Restart will occur
automatically, when temperature falls more than 1°C
below the cutout and cooling demand is present.
This cutout is normally set at 54°C to allow operation
to the absolute maximum temperature capability of the
electromechanical components; however, values be-
tween 37.8 and 54.4°C are acceptable.
Low Ambient Temperature Cutout:
The low ambient temperature cutout is used to select
the ambient temperature below which the chiller may
not operate. If the ambient temperature falls 1°C be-
low this point, the chiller will shutdown. Restart will
occur automatically, when temperature rises more than
1°C above the cutout and cooling demand is present.
If the Dip Switch (S1) on the AMB board is set for
‘STANDARD AMBIENT CONTROL’ the low am-
bient temperature cutout is set at -4°C and is not pro-
grammable.
If the Dip Switch (S1) on the AMB board is set for ‘LOW
AMBIENT CONTROL’, programming of the cutout
between -17.8°C and 10°C is allowed. This allows higher
values than -3.9°C to be programmed to shutdown the
chiller when other cooling methods become operational.
Values below -3.9°C can be used for applications re-
quiring chiller operation at lower temperatures.
Low Leaving Liquid Temperature Cutout:
The low leaving liquid temperature cutout protects the
evaporator from damage due to ice build up caused by
operation below the chilled liquid freezing point.
If the leaving chilled liquid temperature (water or gly-
col) drops below the cutout point, the chiller will shut-
down. The chiller will restart automatically when tem-
perature rises more than 2°C above the cutout point
and cooling demand exists.
If the Dip Switch (S1) on the AMB board is set for
‘WATER’ cooling mode, the cutout is automatically
set at 2.2°C and cannot be reprogrammed.
If the Dip Switch (S1) on the AMB board is set for ‘GLY-
COL’ (Brine) cooling mode, the cutout can be pro-
grammed between -13.3°C and -2.2°C. The cutout should
normally be set to 2°C below the setpoint minus the
range, i.e. 0°C (setpoint) - 1°C (range) - 2°C = -3°C.
High Motor Current Unload Point:
The motor current unload point is used to avoid a high
motor current safety shutdown by unloading a com-
pressor, if current draw approaches the maximum limit
cutout value. The chiller can then continue to run auto-
matically at reduced capacity until the cause of the ex-
cessive current is resolved.
The microprocessor will accept between 30 - 105% for
the unload point. The motor current safety will shut
the compressor down whenever current exceeds 115%.
If the programmable limit is set between 100% and
105% of full load current, this safety will protect against
excessive current causing compressor shutdown due
to extremely high ambient, high chilled liquid tempera-
ture, and condenser malfunction caused by dirt or fan
problems.
If the programmable limit is set below 100% of full
load current, this feature can be used for ‘demand lim-
iting’. This is important when demand limiting is criti-
cal due to power requirements or limitations in the
building.
For the first 60 seconds of operation, the unloading
safety is disabled. After this time, if motor current ex-
ceeds the programmed limit, slide valve current will
be slowly reduced until the motor current drops below
the programmed limit. Additional loading will take
place when motor current drops below 90% of the pro-
grammed threshold.
Typically, this point should be set at 100% for maxi-
mum motor protection, programming for 100% is ad-
visable. When programming values below 100% use
of a leading ‘0’ is required, e.g. 085%.
Anti-Recycle Time:
The anti-recycle timer controls the minimum time be-
tween starts for each compressor. This is the time avail-
L O W
A M B I E N T
T E M P
C U T O U T
=
4 . 0 ° C
L E A V I N G
L I Q U I D
T E M P
C U T O U T
=
2 . 0 ° C
H I G H
M O T O R
C U R R E N T
U N L O A D
=
1 0 0 %
F L A
A N T I
R E C Y C L E
T I M E R
=
6 0 0
S E C S
Micropanel
Содержание YCWS0313SC
Страница 12: ...YORK INTERNATIONAL 12 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT...
Страница 36: ...YORK INTERNATIONAL 36 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT Commissioning...
Страница 86: ...YORK INTERNATIONAL 86 TYPICAL CONTROL PANEL WIRING Maintenance...
Страница 87: ...FORM 201 24 NM2 87 YORK INTERNATIONAL TYPICAL CONTROL PANEL WIRING LD06957 8...
Страница 91: ...FORM 201 24 NM2 91 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT 9...
Страница 101: ...FORM 201 24 NM2 101 YORK INTERNATIONAL SECTION 10 SPARE PARTS This information will be available at a later date 10...
Страница 103: ...FORM 201 24 NM2 103 YORK INTERNATIONAL NOTES 11...