FORM 201.24-NM2
45
YORK INTERNATIONAL
3.1 GENERAL
Pressing the ‘STATUS’ key displays the current chiller
or individual refrigerant system operational status. The
display will show the ‘highest priority’ information as
determined by the microprocessor.
For individual refrigerant system status or fault mes-
sages, the display shows information for up to two re-
frigerant systems.
The main categories of messages are:
• General Status Messages
• Unit Warnings
• Anticipation Control Status Messages
• Chiller Fault Status Messages
• System Fault Status Messages
These messages are described in detail below, with ex-
amples of each display. In each example ‘#’ is used as
applicable to represent the system number where mes-
sages apply to individual systems.
Each display is followed by a brief description of the
message.
3.2 GENERAL STATUS MESSAGES
Unit Switch OFF:
The unit ‘ON/OFF’ switch on the control panel is in
the ‘OFF’ position and the chiller will not run.
Schedule Shutdown:
The chiller has been shut down by the ‘DAILY SCHED-
ULE’ programmed into the ‘CLOCK’.
Remote Controlled Shutdown:
The ISN or RCC (Remote Control Center) has turned
the unit ‘OFF’ through the RS-485 port.
Compressor Running:
The respective compressor is running due to demand.
System Switch OFF:
The system switch on the AMB board for the respec-
tive system is in the ‘OFF’ position.
A system can only run if the system switch is in the
‘ON’ position. The switches for systems 1 and 2 should
normally be in the ‘ON’ position for all models. Switches
for systems 3 and 4 should only be in the ‘ON’ position
for three and four system models respectively.
29023a
3. STATUS KEY
U N I T
S W I T C H
I S
I N
T H E
O F F
P O S I T I O N
D A I L Y
S C H E D U L E
S H U T D O W N
R E M O T E
C O N T R O L L E D
S H U T D O W N
S Y S
#
C O M P
R U N N I N G
S Y S
#
C O M P
R U N N I N G
S Y S
#
S W I T C H
O F F
S Y S
#
S W I T C H
O F F
7
Содержание YCWS0313SC
Страница 12: ...YORK INTERNATIONAL 12 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT...
Страница 36: ...YORK INTERNATIONAL 36 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT Commissioning...
Страница 86: ...YORK INTERNATIONAL 86 TYPICAL CONTROL PANEL WIRING Maintenance...
Страница 87: ...FORM 201 24 NM2 87 YORK INTERNATIONAL TYPICAL CONTROL PANEL WIRING LD06957 8...
Страница 91: ...FORM 201 24 NM2 91 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT 9...
Страница 101: ...FORM 201 24 NM2 101 YORK INTERNATIONAL SECTION 10 SPARE PARTS This information will be available at a later date 10...
Страница 103: ...FORM 201 24 NM2 103 YORK INTERNATIONAL NOTES 11...