YORK INTERNATIONAL
80
Micropanel
The optional Remote Reset option would be used when
reset of the chilled liquid setpoint is required and a
PWM signal (timed contact closure) cannot be supplied
by an Energy Management System. The Remote Temp.
Reset Board will convert a voltage, current, or contact
not operate. If the ambient temperature rises 1°C above
signal that is available from an EMS to a PWM signal,
and every 80 seconds provide a PWM input to the mi-
croboard. Figure 3 shows a diagram of the field and
factory electrical connections.
If a 0 - 10VDC signal is available, it is applied to ter-
minals A+ and A-, and jumpers are applied to JU4
and JU2 on the reset board. This dc signal is condi-
tioned to a 1 - 11 second PWM output and supplied to
the PWM input on the microboard at CTB 1 terminals
13 - 20. To calculate the reset chilled liquid setpoint for
values between 0VDC and 10VDC use the following
formula:
setpoint = local chilled liquid se °reset
°
reset = (dc voltage signal) x (*Max Reset Value)
10
Example:
Local Chilled Liquid Setpoint = 45°F (7.22°C)
*Max Reset Value = 20°F (11.11°C)
Input Signal = 6 VDC
(English)
°
reset = 6VDC x 20°F = 12
°
F reset
10
setpoint = 45 °F + 12 °F = 57°F
(Metric)
°
reset = 6VDC x 11. 11°C = 6.67°C reset
10
setpoint = 7.22°C + 6.67°C = 13.89°C
I
f a 4-20mA signal is available, it is applied to terminals
A+ and A- and jumpers are applied to JU5 and JU3
on the reset board. The mA signal is conditioned to a
1-11 second PWM output. The PWM output is then sup-
plied to the PWM input on the microboard at CTB 1 ter-
minals 13 - 20. To calculate the chilled liquid setpoint for
values between 4mA and 20 ma use the following for-
mula:
setpoint = local chilled liquid se °reset
°reset = (mA signal - 4) x (*Max Reset Value)
16
If the Contact Closure input is used. The connections
are made to terminals C and D and only jumper JUI
must be in place on the reset board. This input is used
when a
single reset value is needed. When the contacts
are closed, the remote temperature reset board will con-
vert this contact closure to a PWM signal that is applied
to CTB 1 terminals 13 - 20.
To set the PWM output, the contacts must be closed on
inputs C - D, and potentiometer R11 (located on the front
edge of the PC board) is adjusted to 10VDC as mea-
sured at TP3 to terminal 10 on the circuit board. The
reset value will be the “Max EMS-PWM Remote Temp.
Reset” setpoint value programmed in the SETPOINTS
section under the Cooling Setpoints key.
NOTE: The coil of any added relay used for reset must
be suppressed to prevent possible component
damage. Use YORK PN031-00808-000
suppressor.
*Max Reset Value is the “Max EMS-PWM Remote Temp. Reset” setpoint value described in the programming section under Cooling Setpoints.
Programmable values are from 2°F to 40°F (1.11°C to 11.11°C).
A 240-24 Volt Ratio Transformer (T3)
is used to derive nominal 12 volt out-
put from the 120 volt supply.
Example:
Local Chilled Liquid Setpoint = 45° (7.22°C)
*Max Reset Value = 10°F (5.56°C)
Input Signal = 12 mA
(English)
°reset = 8mA x 10°F = 5°F reset
16
setpoint = 45°F + 5°F = 50°F
(Metric)
°reset = 8mA x 5.56°C = 2.78°C reset
16
setpoint = 7.22°C + 2.78°C = 10.0°C
Содержание YCWS0313SC
Страница 12: ...YORK INTERNATIONAL 12 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT...
Страница 36: ...YORK INTERNATIONAL 36 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT Commissioning...
Страница 86: ...YORK INTERNATIONAL 86 TYPICAL CONTROL PANEL WIRING Maintenance...
Страница 87: ...FORM 201 24 NM2 87 YORK INTERNATIONAL TYPICAL CONTROL PANEL WIRING LD06957 8...
Страница 91: ...FORM 201 24 NM2 91 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT 9...
Страница 101: ...FORM 201 24 NM2 101 YORK INTERNATIONAL SECTION 10 SPARE PARTS This information will be available at a later date 10...
Страница 103: ...FORM 201 24 NM2 103 YORK INTERNATIONAL NOTES 11...