201
JOHNSON CONTROLS
FORM 201.21-NM3 (616)
6
CHILLER ELECTRONIC COMPONENTS (CON'T)
Once communications is established, the Chiller Control
Board will send a data packet on the data link once every
second at 9600 baud. This data packet will include run,
stop, and speed commands as well as request operating
data from the VSD. Operating data returned by the VSD
will include individual motor currents, motor %FLA’s,
output frequency, compressor motor temperature, and
fault information related to internal VSD operating
parameters such as DC bus voltage, IGBT baseplate
temperatures, VSD internal ambient, pre-charge relay
status, power supply status, run relay status, motor
overload, and supply single phase. The Chiller Control
Board will poll the VSD Logic Board for information
continuously while the chiller is running.
IGBT GATE DRIVER BOARDS
The IGBT Gate Driver Boards provide the ON and
OFF gating pulses to the IGBT’s. The gating signals
originate from the VSD Logic Board and are changed
in level by the IGBT Gate Driver Board. The IGBT’s
in the inverter section of the VSD, change the DC Link
voltage to a variable Voltage and Frequency output to
the motor, to control the compressor motor speed. The
IGBT Gate Driver Boards also provides VCE SAT
detection (short circuit detection) to safely turn off the
IGBT’s during a short circuit condition. When a short
circuit occurs, the voltage (VCE SAT) across the IGBT
increases as a result of the high current. The IGBT Gate
Driver Board is an integral part of the IGBT assembly
for each compressor.
LD10613
LD10617
CURRENT TRANSFORMERS
A current transformer on each phase sends current
signals proportional to phase current to the VSD Logic
Board. The output of each CT is buffered, scaled, and
sent to RMS to DC converters. These signals are then
sent to an A-D converter, scaled, and sent to the Chiller
Control board for current display and current limiting
control.
The highest current is also compared to the setting of the
Overload Adjustment Potentiometer on the VSD Logic
Board for overload safety sensing.
CURRENT
TRANSFORMERS
Содержание YCAV0267E
Страница 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Страница 63: ...63 JOHNSON CONTROLS FORM 201 21 NM3 616 ELEMENTARY CONTROL WIRING DIAGRAM 3 COMPRESSOR CON T LD12552 ...
Страница 67: ...67 JOHNSON CONTROLS FORM 201 21 NM3 616 LD12556 POWER ELEMENTARY DIAGRAM 3 COMPRESSOR YCAV CHILLER CON T 6 ...
Страница 72: ...72 JOHNSON CONTROLS FORM 201 21 NM3 616 035 20326 006 REV TECHNICAL DATA LD11125 LOCATION LABEL ...
Страница 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Страница 88: ...88 JOHNSON CONTROLS FORM 201 21 NM3 616 LOCATION LABEL TECHNICAL DATA 035 20890 008 REV LD11140 ...
Страница 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Страница 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Страница 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Страница 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Страница 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Страница 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Страница 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Страница 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Страница 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...