UNIT SETUP MODE
MICRO PANEL
Unit Setup Mode will allow the programming all of the
programmable values that the user should never change.
These will either be programmed at the factory or by
service personnel on the job.
TABLE 19 - UNIT SETUP PROGRAMMABLE VALUES
SETUP MODE VALUE
PROGRAMMABLE RANGE
DEFAULT
Sys 1 Number of Cond Fans
4 to 6
6
Sys 2 Number of Cond Fans
4 to 6
6
Sys 3 Number of Cond Fans
4 to 6
6
Sys 4 Number of Cond Fans
4 to 6
6
Compressor 1 Operating hours
0 to 99,999
0
Compressor 2 Operating hours
0 to 99,999
0
Compressor 3 Operating hours
0 to 99,999
0
Compressor 4 Operating hours
0 to 99,999
0
Compressor 1 Starts
0 to 99,999
0
Compressor 2 Starts
0 to 99,999
0
Compressor 3 Starts
0 to 99,999
0
Compressor 4 Starts
0 to 99,999
0
Clear History Buffers
Yes/ No
-
Remote Temp Reset Option
Disabled/Enabled
Disabled
Remote Current Limit Option
Disabled/Enabled
Disabled
Sound Limit Option
Disabled/Enabled
Disabled
Remote Inputs Service Time
5 Min - 60 Min
15 Min
Sys 1 Motor Sensor to Ignore
See Below
None
Sys 2 Motor Sensor to Ignore
See Below
None
Sys 3 Motor Sensor to Ignore
See Below
None
Sys 4 Motor Sensor to Ignore
See Below
None
The following messages will be displayed for the Unit
Setup Mode in the order they appear. The first group
of displays relates to setup parameters that relate to unit
configuration and factory setpoints.
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
SYS 1 NUMBER OF COND FANS
= X
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
SYS 2 NUMBER OF COND FANS
= X
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
SYS 3 NUMBER OF COND FANS
= X
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
SYS 4 NUMBER OF COND FANS
= X
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
COMP 1 OPERATING HOURS
= XXXXX
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
COMP 2 OPERATING HOURS
= XXXXX
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
COMP 3 OPERATING HOURS
= XXXXX
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
COMP 4 OPERATING HOURS
= XXXXX
This mode may be entered by pressing the PROGRAM
key, entering the password 4245, and pressing the √
(ENTER) key. TABLE 19 lists the values that can be
programmed in this mode. Details relating to the actual
message follow the table.
Содержание YCAV0267E
Страница 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Страница 63: ...63 JOHNSON CONTROLS FORM 201 21 NM3 616 ELEMENTARY CONTROL WIRING DIAGRAM 3 COMPRESSOR CON T LD12552 ...
Страница 67: ...67 JOHNSON CONTROLS FORM 201 21 NM3 616 LD12556 POWER ELEMENTARY DIAGRAM 3 COMPRESSOR YCAV CHILLER CON T 6 ...
Страница 72: ...72 JOHNSON CONTROLS FORM 201 21 NM3 616 035 20326 006 REV TECHNICAL DATA LD11125 LOCATION LABEL ...
Страница 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Страница 88: ...88 JOHNSON CONTROLS FORM 201 21 NM3 616 LOCATION LABEL TECHNICAL DATA 035 20890 008 REV LD11140 ...
Страница 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Страница 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Страница 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Страница 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Страница 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Страница 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Страница 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Страница 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Страница 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...