In cases where temperature is dropping too fast, when
temperature is within the desired control range, the
Chiller Control Board microprocessor will be required
to make decisions regarding speed changes under
conditions where the “error” and “rate” conflict. For
example, the Chiller Control Board microprocessor
may elect to reduce the speed of the compressor(s) if
the error is “0” (temperature is at Setpoint), while the
rate of change of chilled liquid temperature is “negative“
(falling). The Chiller Control Board microprocessor
may also elect to hold capacity when error is “positive”
(temperature is above Setpoint, but not above Setpoint
+ CR) because the rate of change of chilled liquid is
“negative” (falling). TABLE 5 illustrates these
conditions.
OPTIONAL HIGH IPLV CAPACITY CONTROL (CON'T)
(Loading/Unloading and starting additional compressors)
TABLE 5 - FUZZY LOGIC LOADING/UNLOADING
VS. ERROR
NEGATIVE
ERROR
ZERO
ERROR
POSITIVE
ERROR
NEGATIVE
RATE
UNLOAD UNLOAD
HOLD
ZERO
RATE
UNLOAD
HOLD
HOLD
POSITIVE
RATE
HOLD
LOAD
LOAD
When temperature is significantly below the Setpoint
– CR/2, the Chiller Control Board microprocessor will
reduce the speed of the compressor(s) to unload the
chiller by 2.0 Hz every 2 seconds. If temperature drops
to within 1.0°F above the Low Chilled Liquid Tempera-
ture Cutout, the Chiller Control Board microprocessor
will unload at the rate of 4.0 Hz every 2 seconds.
As the temperature rises toward Setpoint – CR, the
Chiller Control Board microprocessor’s fuzzy logic will
begin factoring in the rate of change before continuing to
unload. If the rate of change is rising too fast and there
is potential for overshoot, the Chiller Control Board
microprocessor may elect not to decrease speed.
In cases where temperature is rising too fast, when tem-
perature is within the desired control range, the Chiller
Control Board microprocessor will be required to make
decisions regarding speed changes under conditions
where the “error” and “rate” conflict. For example, the
Chiller Control Board microprocessor may elect to in-
crease the speed of the compressor(s) if the error is “0”
(temperature is at Setpoint), while the rate of change
of chilled liquid temperature is “positive” (rising). The
Chiller Control Board microprocessor may also elect to
hold capacity when error is “negative” (temperature is
below Setpoint) because the rate of change of chilled
liquid is “positive” (rising). TABLE 5 illustrates these
conditions and the response from the Chiller Control
Board microprocessor.
HOT WATER STARTS
On a hot water start under "best" case conditions, as-
suming power has not been removed and the 120 sec
timer does not inhibit starting, the design of the control
algorithm for a 2 compressor High IPLV leaving chilled
liquid capacity control allows full loading of a chiller in
slightly more than 6 minutes, regardless of the number
of compressors, if all the compressors start at the same
time. This time period assumes load limiting does not
affect the loading sequence and the ambient is above
40°F.
7
Содержание YCAV0267E
Страница 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Страница 63: ...63 JOHNSON CONTROLS FORM 201 21 NM3 616 ELEMENTARY CONTROL WIRING DIAGRAM 3 COMPRESSOR CON T LD12552 ...
Страница 67: ...67 JOHNSON CONTROLS FORM 201 21 NM3 616 LD12556 POWER ELEMENTARY DIAGRAM 3 COMPRESSOR YCAV CHILLER CON T 6 ...
Страница 72: ...72 JOHNSON CONTROLS FORM 201 21 NM3 616 035 20326 006 REV TECHNICAL DATA LD11125 LOCATION LABEL ...
Страница 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Страница 88: ...88 JOHNSON CONTROLS FORM 201 21 NM3 616 LOCATION LABEL TECHNICAL DATA 035 20890 008 REV LD11140 ...
Страница 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Страница 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Страница 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Страница 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Страница 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Страница 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Страница 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Страница 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Страница 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...