219
JOHNSON CONTROLS
FORM 201.21-NM3 (616)
LOAD LIMITING CONTROL (CON'T)
Suction Pressure Load Limiting/Unloading
Suction pressure load limiting helps to protect the
evaporator from freezing. A system is permitted to load
normally as long as the Suction Pressure is above the
Suction Pressure 2 PSIG. Between
2 PSIG and the Cutout, loading is inhibited, even though
increased loading is required. Between the Suction
pressure Cutout and Suction Pressure Cutout – 10 PSIG,
forced unloading is performed every 2 seconds accord-
ing to TABLE 8 below. This situation would occur if
the suction pressure cutout transient override control is
in effect (See Low Suction Pressure Cutout, Page 253).
The suction pressure cutout is programmed under the
Program key. The default Suction Pressure Cutout is
set at 24.0 PSIG.
TABLE 8 - SUCTION PRESSURE
LOAD LIMITING/UNLOADING
SUCTION PRESSURE
UN-
LOADING
Suction Pressure is between
2 PSIG
&
Suction Pressure Cutout
0 Hz
Suction Pressure Cutout- 1 PSIG
1 Hz
Suction Pressure Cutout- 2 PSIG
2 Hz
Suction Pressure Cutout- 3 PSIG
3 Hz
Suction Pressure Cutout- 4 PSIG
4 Hz
Suction Pressure Cutout- 5 PSIG
5 Hz
Suction Pressure Cutout- 6 PSIG
6 Hz
Suction Pressure Cutout- 7 PSIG
7 Hz
Suction Pressure Cutout- 8 PSIG
8 Hz
Suction Pressure Cutout- 9 PSIG
9 Hz
Suction Pressure Cutout- 10 PSIG
10 Hz
Suction pressure load limiting is active at start-up, to
only prevent loading of the compressors. Suction pres-
sure limit unloading will not occur until the system run
time reaches 5 minutes of operation to allow the system
to stabilize.
VSD Internal Ambient Temperature
Load Limiting
VSD Internal Ambient temperature limiting helps pre-
vent the unit from tripping on the high internal cabinet
temperature safety. A system is permitted to load nor-
mally as long as the VSD Internal Ambient is below the
VSD Internal Ambient Cutout – 3°F. Between VSD
Internal Ambient Cutout – 3°F and the VSD Internal
Ambient Cutout – 2°F, loading is inhibited, even though
increased loading is required. Between the VSD Internal
Ambient Cutout – 2°F and the VSD Internal Ambient
Cutout, forced unloading is performed every 2 seconds
according to TABLE 9 below. The VSD Internal Ambi-
ent Safety Cutout is 158°F.
TABLE 9 - VSD INTERNAL AMBIENT
LOAD LIMITING/UNLOADING
VSD INTERNAL AMBIENT
TEMPERATURE
UN-
LOADING
Internal Ambient Temp. is between
Cutout- 3ºF
&
Internal Ambient Cutout- 2ºF
0 Hz
Internal Ambient Cutout- 1.8ºF
1 Hz
Internal Ambient Cutout- 1.6ºF
2 Hz
Internal Ambient Cutout- 1.4ºF
3 Hz
Internal Ambient Cutout- 1.2ºF
4 Hz
Internal Ambient Cutout- 0ºF
5 Hz
Internal Ambient Cutout- 0.8ºF
6 Hz
Internal Ambient Cutout- 0.6ºF
7 Hz
Internal Ambient Cutout- 0.4ºF
8 Hz
Internal Ambient Cutout- 0.2ºF
9 Hz
Internal Ambient Cutout
10 Hz
7
Содержание YCAV0267E
Страница 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Страница 63: ...63 JOHNSON CONTROLS FORM 201 21 NM3 616 ELEMENTARY CONTROL WIRING DIAGRAM 3 COMPRESSOR CON T LD12552 ...
Страница 67: ...67 JOHNSON CONTROLS FORM 201 21 NM3 616 LD12556 POWER ELEMENTARY DIAGRAM 3 COMPRESSOR YCAV CHILLER CON T 6 ...
Страница 72: ...72 JOHNSON CONTROLS FORM 201 21 NM3 616 035 20326 006 REV TECHNICAL DATA LD11125 LOCATION LABEL ...
Страница 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Страница 88: ...88 JOHNSON CONTROLS FORM 201 21 NM3 616 LOCATION LABEL TECHNICAL DATA 035 20890 008 REV LD11140 ...
Страница 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Страница 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Страница 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Страница 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Страница 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Страница 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Страница 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Страница 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Страница 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...