191
JOHNSON CONTROLS
FORM 201.21-NM3 (616)
6
Changing the programming of this
feature requires the date and time to be
set on the chiller prior to programming.
Additional information regarding this
message is provided in the ENABLING
HIGH IPLV MODE information on
Page 305.
9. Program the required options into the Panel for
the desired operating requirements. See Page 284.
Record the values below:
Display Language = ______________________
Chilled Liquid Mode = ____________________
Local/Remote Mode = ____________________
Display Units = _________________________
Lead/Lag Control = _______________________
Remote Temperature Reset = _______________
Remote Current Reset = ___________________
Remote Sound Limit =_____________________
Low Ambient Cutout =_____________________
Damage to the chiller could result if the
options are improperly programmed.
UNIT WARNING: OPTIMIZED EFFICIENCY
DISABLED – CONTACT YORK REPRESENTATIVE
EQUIPMENT START-UP CHECK SHEET (CON'T)
PROGRAMMED VALUES
10. Program the required operating values into the
micro for cutouts, safeties, etc. and record them in
the chart below. See Page 281 for details. Record
these values in the chart below.
Suction Press Cutout =
________________________ PSIG (kPa)
Low Ambient Cutout =
________________________ °F (°C)
Leaving Chilled Liquid Temp Cutout =
________________________ °F (°C)
Motor Current Limit =
________________________% FLA
Pulldown Current Limit Time =
________________________MIN
Suction Superheat Setpoint =
________________________°F (°C)
Remote Unit ID # =
___________________________
Sound Limit Setpoint =
__________________________%
CHILLED LIQUID SETPOINT
11 Program the Chilled Liquid Setpoint/Range and
record:
Local Cooling Setpoint =
____________________ °F (°C)
Local Cooling Range =
_________ to _________ °F (°C)
Maximum Remote Temp Reset =
_________ to _________ °F (°C)
DATE/TIME, DAILY SCHEDULE, AND CLOCK
JUMPER
12 Set the Date and Time.
13. Program the Daily Schedule start and stop times.
If the following message appears when the STATUS
key is pressed, immediately contact YORK Product
Technical Support. The appearance of this message
indicates the chiller is a HIGH IPLV chiller operat-
ing in STANDARD IPLV control.
Содержание YCAV0267E
Страница 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Страница 63: ...63 JOHNSON CONTROLS FORM 201 21 NM3 616 ELEMENTARY CONTROL WIRING DIAGRAM 3 COMPRESSOR CON T LD12552 ...
Страница 67: ...67 JOHNSON CONTROLS FORM 201 21 NM3 616 LD12556 POWER ELEMENTARY DIAGRAM 3 COMPRESSOR YCAV CHILLER CON T 6 ...
Страница 72: ...72 JOHNSON CONTROLS FORM 201 21 NM3 616 035 20326 006 REV TECHNICAL DATA LD11125 LOCATION LABEL ...
Страница 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Страница 88: ...88 JOHNSON CONTROLS FORM 201 21 NM3 616 LOCATION LABEL TECHNICAL DATA 035 20890 008 REV LD11140 ...
Страница 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Страница 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Страница 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Страница 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Страница 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Страница 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Страница 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Страница 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Страница 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...