JOHNSON CONTROLS
FORM 201.21-NM3 (616)
2
Display
The display consists of a liquid crystal 2 line by 40
characters per line display, with
backlighting for outdoor
viewing of operating parameters and program points.
Parameters are displayed in 5 languages in either Eng-
lish (°F and PSIG) or Metric (°C and Bars) units, and for
each circuit, the following items can be displayed:
• Entering and leaving chilled liquid, and ambient
temperature.
• Day, date and time. Daily start/stop times. Holiday
and Manual Override status.
• Compressor operating hours and starts. Automatic or
manual lead/lag. Lead compressor identification.
• Run permissive status. Compressor run status.
• Anti-recycle timers.
• System suction (and suction superheat), discharge
(and discharge superheat), and oil pressures and
temperatures.
• Percent full load compressor motor current and
average motor current. Compressor motor speed
(frequency).
• Cutout status and setpoints for: supply chilled liquid
temperature, low suction pressure, high discharge
pressure and temperature, high oil temperature, low
ambient, and low leaving liquid temperature.
• Unloading limit setpoints for high discharge pres
-
sure and compressor motor current.
• Status of: evaporator heater, condenser fans, load/
unload timers, and chilled water pump.
• “Out of range” message.
• Up to 10 fault shutdown histories.
Keypad
An operator keypad allows complete control of the
system from a central location. The keypad utilizes
an overlay to allow use in 5 languages. The keypad is
a color-coded, 36 button, sealed keypad with keys for
Display, Entry, Setpoints, Clock, Print, Program, Unit
ON/OFF and other functions. Details on a few of the
keys follow.
Status –
Allows viewing present unit or system status
displayed by the microprocessor.
Entry –
Numeric keypad and supporting keys used to
confirm Setpoint changes, cancel inputs, advance day,
and change AM/PM.
Setpoints –
For setting chilled liquid temperature,
chilled liquid range, remote reset temperature range.
Date/Time –
Used to set time, daily or holiday start/stop
schedule, manual override for servicing, and sound
limiting schedule.
Print –
Used to display or print operating data or sys-
tem fault shutdown history for last ten faults. Printouts
are generated through an RS-232 port via a separate
printer.
Program –
For setting low leaving liquid temperature
cutout, average motor current limit, and pulldown de-
mand limit.
Displays are also provided for programming low am-
bient cutout, low suction pressure cutout, superheat
setpoint, etc., under the PROGRAM key.
Unit Switch
A master unit switch allows activation or de-activation
of the chiller system. Separate system switches for con-
trolling each system are provided as part of the chiller
control panel keypad.
Содержание YCAV0267E
Страница 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Страница 63: ...63 JOHNSON CONTROLS FORM 201 21 NM3 616 ELEMENTARY CONTROL WIRING DIAGRAM 3 COMPRESSOR CON T LD12552 ...
Страница 67: ...67 JOHNSON CONTROLS FORM 201 21 NM3 616 LD12556 POWER ELEMENTARY DIAGRAM 3 COMPRESSOR YCAV CHILLER CON T 6 ...
Страница 72: ...72 JOHNSON CONTROLS FORM 201 21 NM3 616 035 20326 006 REV TECHNICAL DATA LD11125 LOCATION LABEL ...
Страница 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Страница 88: ...88 JOHNSON CONTROLS FORM 201 21 NM3 616 LOCATION LABEL TECHNICAL DATA 035 20890 008 REV LD11140 ...
Страница 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Страница 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Страница 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Страница 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Страница 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Страница 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Страница 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Страница 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Страница 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...