<4. Explanation of Basic Item>
4-7
IM 12A01A02-72E
3rd Edition : Oct. 01, 2015-00
4.6
Setting the AI Function Blocks
The AI function block is a unit of the software.
During execution, it incorporates data from the SENSOR transducer block. After execution, it
updates analog outputs and processes newly generated alarms. AI function blocks can provide a
discrete output which shows the status of LO, LO_LO, HI, or HI_HI. In terms of function, there is
no difference between the three AI function blocks provided in FLXA21.
n
Function Blocks
The AI function block, via the Channel, incorporates analog signals from the transducer block,
performs scaling processing, filtering, signal linearization, fail safe control and alarm processing
before outputting. It has the function to generate a discrete output. Figure 4.1 presents the AI
function block.
Simulate.Enable
MODE_BLK. Actual
Simulate
Value, Status
PV from TB
Value, Status
Value, Status
Scaling
PV_SCALE
Linearization
LIN_TYPE
Scaling
OUT_SCALE
Filter
PV_FTIME
Limit Check
HI, HI_HI
LO, LO_LO
Fail
Safe
OUT
OUT
AUTO
MAN
OUT
OS
Figure 4.1
Diagram of the AI Functional Block
n
Setting the output scale
As explained in section 4.2.4 the OUT_SCALE can used to convert the channel’s value to a
different scale.
The default value is 0.0 to 100.0%.
Change this if necessary.
For AI1 set L_TYPE to Direct
With the FLXA21, the channel values are displayed on the display indicator, independent of the
scaling in the AI blocks.
n
Setting the output mode
Access the L_TYPE parameter.
Set the output mode.
0: Direct
(no linearisation)
10: Square root
(Square root extraction
output value)
n
Setting the damping time constant
Access the PV_FTIME parameter.
Set the damping time (in seconds).