<4. Explanation of Basic Item>
4-6
IM 12A01A02-72E
3rd Edition : Oct. 01, 2015-00
4.5
Setting and change of basic parameters
This section describes the procedure taken to set and change the parameters for each block.
Obtaining access to each parameter differs depending on the configuration system used.
For details, refer to the instruction manual for each configuration system.
Set the Target of block mode (MODE_BLK) to Auto,
Man or O/S (*Note 2) according to the Write Mode of the
parameter to be set or changed.
When “actual mode” has changed (*Note 1),
data associated with the function block
can be maintenanced.
Access the block mode (MODE_BLK) of each block.
back to Auto (*Note 2).
Set the Target (*Note 1) of block mode
CAUTION
Do not turn the power of the device OFF immediately after parameter setting. When the
parameters are saved to the EEPROM, the redundant processing is executed for an
improvement of reliability. Should the power be turned OFF within 60 seconds after setting of
parameters, changed parameters are not saved and may return to their original values.
Refer to the tables in Chapter 6 for details of the Write Mode for each block.
AI Function Block Transducer Block
Physical Block
Automatic (Auto)
Yes
Yes
Yes
Manual (Man)
Yes
Out of Service (O/S)
Yes
Yes
Yes