C4.3 Limiting the Set Point
You can set upper limit and lower limit for the control set point (CSP).
This feature is useful in situations where it is desirable to limit the control set point within
a certain temperature range, depending on the characteristics of equipment and
materials involved.
-
Set the SP Upper Limit (SPH) parameter to the desired upper limit and the SP Lower
Limit (SPL) parameter to the desired lower limit.
The SP limit function is always enabled, regardless of the remote/local selection.
It is always enabled for the secondary loop in cascade control, regardless of the
Automatic/manual/cascade selection.
Table C4.3 Parameters Related to the Set Point Limit Function
Data Position Number
Symbol Description Unit
Data
Range
Default
Value Attribute Stored
Loop1 Loop2 Loop3 Loop4
103 303 503 703 CSP Control
set
point
Industrial
unit
PRL to PRH
—
RO
—
164
364 564 764
SPH
Upper SP limit
Industrial
unit
PRL to PRH If SPL<SPH.
If SPL
≥
SPH, CSP is always
equal to SPL.
PRH
RW
165 365 565 765
SPL
Lower SP limit
PRL
RW
Set the SP limits such that SPL < SPH.
If SPL
≥
SPH, then the control set point (CSP) will always be equal to SPL.
If SPH and SPL are used in the secondary loop in cascade control, align the Upper
Output Limit (OH) and Lower Output Limit (OL) of the primary loop with SPH and SPL of
the secondary loop respectively. Otherwise, the control set point of the secondary loop
may be constrained by SPH or SPL of the secondary loop, resulting in a large PV
overshoot in the primary loop. For instance, if the SPH of the secondary loop is 50% of
the PV range between PRH and PRL, it is recommended that OH of the primary loop be
set to 50%.
Содержание F3CU04-0S
Страница 2: ...Blank Page...
Страница 18: ...Blank Page...
Страница 32: ...Blank Page...
Страница 34: ...Blank Page...
Страница 50: ...Blank Page...
Страница 90: ...Blank Page...
Страница 97: ...B3 7 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 2 Sample Program for Setting Controller Parameters 2 2...
Страница 100: ...B3 10 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 3 Sample Program for Setting I O Parameters 2 3...
Страница 101: ...B3 11 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 3 Sample Program for Setting I O Parameters 3 3...
Страница 110: ...B4 2 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 2 5...
Страница 111: ...B4 3 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 3 5...
Страница 112: ...B4 4 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 4 5...
Страница 113: ...B4 5 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 5 5...
Страница 118: ...Blank Page...
Страница 130: ...Blank Page...
Страница 204: ...Blank Page...
Страница 215: ...C8 1 IM 34M06H62 02E 2nd Edition June 2008 00 C8 Alarm Function This chapter describes the alarm function of the module...
Страница 222: ...Blank Page...
Страница 224: ...Blank Page...
Страница 228: ...Blank Page...
Страница 230: ...Blank Page...
Страница 232: ...Blank Page...
Страница 234: ...Blank Page...
Страница 240: ...Blank Page...
Страница 242: ...Blank Page...
Страница 254: ...Blank Page...
Страница 258: ...Blank Page...
Страница 260: ...Blank Page...