C8-3
IM 34M06H62-02E
2nd Edition : June 2008-00
Table C8.1 Alarm Parameters
Data Position Number
Symbol
Description
Unit
Data Range
Default
Value Attribute Stored
See
Also
Loop 1 Loop 2 Loop 3 Loop 4
102
302
502
702
PV
Process value
Industrial
unit
-5.0 to 105.0% of (PRL to
PRH)
—
RO
—
C3
103
303
503
703
CSP
Control set point
Industrial
unit
PRL to PRH
—
RO
—
C4
107
307
507
707
CSPNO Current SP number
None 1 to 4
—
RO
—
C4
109
309
509
709 ALM.STUS Alarm status
None
Each bit represents an alarm
condition, which is either on
or off.
—
RO
—
C8.1
128
328
528
728
SPNO SP number selection
None 1 to 4
1
RW
—
C4.1
202
402
602
802
1.A1
Alarm 1 preset value
Industrial
unit
-30000 to 30000
PRH
RW
C8.4
203
403
603
803
1.A2
Alarm 2 preset value
PRL
RW
C8.4
204
404
604
804
1.A3
Alarm 3 preset value
PRH
RW
C8.4
205
405
605
805
1.A4
Alarm 4 preset value
PRL
RW
C8.4
222
422
622
822
2.A1
Alarm 1 preset value
Industrial
unit
-30000 to 30000
PRH
RW
C8.4
223
423
623
823
2.A2
Alarm 2 preset value
PRL
RW
C8.4
224
424
624
824
2.A3
Alarm 3 preset value
PRH
RW
C8.4
225
425
625
825
2.A4
Alarm 4 preset value
PRL
RW
C8.4
242
442
642
842
3.A1
Alarm 1 preset value
Industrial
unit
-30000 to 30000
PRH
RW
C8.4
243
443
643
843
3.A2
Alarm 2 preset value
PRL
RW
C8.4
244
444
644
844
3.A3
Alarm 3 preset value
PRH
RW
C8.4
245
445
645
845
3.A4
Alarm 4 preset value
PRL
RW
C8.4
262
462
662
862
4.A1
Alarm 1 preset value
Industrial
unit
-30000 to 30000
PRH
RW
C8.4
263
463
663
863
4.A2
Alarm 2 preset value
PRL
RW
C8.4
264
464
664
864
4.A3
Alarm 3 preset value
PRH
RW
C8.4
265
465
665
865
4.A4
Alarm 4 preset value
PRL
RW
C8.4
281
481
681
881
AL1
Alarm 1 type
None
0: OFF
1: Upper limit
2: Lower limit
3: Upper deviation limit
4: Lower deviation limit
7: Upper/lower deviation
limit
8: Deviation range
11: Upper limit with waiting
12: Lower limit with waiting
13: Upper deviation limit with
waiting
14: Lower deviation limit with
waiting
17: Upper/lower deviation
limit with waiting
18: Deviation range with
waiting
1
RW
C8.1
282
482
682
882
AL2
Alarm 2 type
2
RW
C8.1
283
483
683
883
AL3
Alarm 3 type
1
RW
C8.1
284
484
684
884
AL4
Alarm 4 type
2
RW
C8.1
285
485
685
885
HY1
Alarm 1 hysteresis
Industrial
unit
0 to (PRH - PRL)
(PRH -
PRL) x
0.5%
RW
C8.1
286
486
686
886
HY2
Alarm 2 hysteresis
RW
C8.1
287
487
687
887
HY3
Alarm 3 hysteresis
RW
C8.1
288
488
688
888
HY4
Alarm 4 hysteresis
RW
C8.1
289
489
689
889
DLY1
Alarm 1 ON delay
second 0 to 999
0
RW
C8.3
290
490
690
890
DLY2
Alarm 2 ON delay
RW
C8.3
291
491
691
891
DLY3
Alarm 3 ON delay
RW
C8.3
292
492
692
892
DLY4
Alarm 4 ON delay
RW
C8.3
Table C8.2 Alarm Input Relays
Input relay Number
X
nn *
Symbol
Description
Data Range
Interrupt
Loop 1 Loop 2 Loop 3 Loop 4
01
09
17
25
ALM1.R Alarm 1
0: Normal, 1: Alarm 1
02
10
18
26
ALM2.R Alarm 2
0: Normal, 1: Alarm 2
*
denotes the slot number where the module is installed.
Alarms 3 and 4 have no associated input relay. Their status is indicated by the
corresponding bit of ALM.STUS.
Содержание F3CU04-0S
Страница 2: ...Blank Page...
Страница 18: ...Blank Page...
Страница 32: ...Blank Page...
Страница 34: ...Blank Page...
Страница 50: ...Blank Page...
Страница 90: ...Blank Page...
Страница 97: ...B3 7 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 2 Sample Program for Setting Controller Parameters 2 2...
Страница 100: ...B3 10 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 3 Sample Program for Setting I O Parameters 2 3...
Страница 101: ...B3 11 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 3 Sample Program for Setting I O Parameters 3 3...
Страница 110: ...B4 2 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 2 5...
Страница 111: ...B4 3 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 3 5...
Страница 112: ...B4 4 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 4 5...
Страница 113: ...B4 5 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 5 5...
Страница 118: ...Blank Page...
Страница 130: ...Blank Page...
Страница 204: ...Blank Page...
Страница 215: ...C8 1 IM 34M06H62 02E 2nd Edition June 2008 00 C8 Alarm Function This chapter describes the alarm function of the module...
Страница 222: ...Blank Page...
Страница 224: ...Blank Page...
Страница 228: ...Blank Page...
Страница 230: ...Blank Page...
Страница 232: ...Blank Page...
Страница 234: ...Blank Page...
Страница 240: ...Blank Page...
Страница 242: ...Blank Page...
Страница 254: ...Blank Page...
Страница 258: ...Blank Page...
Страница 260: ...Blank Page...