B3-14
IM 34M06H62-02E
2nd Edition : June 2008-00
B3.3.2 Preparing for PID Control
To perform PID control without dynamic auto-tuning, you must manually set the PID
control parameters, namely, the Proportional Band (PB), Integral Time (TI) and Derivative
Time (TD) parameters according to the characteristics of the controlled object. If you
specify inappropriate PID parameter values, you will not be able to achieve the desired
control. You may directly change the PB, TI, and TD registers, or use the auto-tuning
function to let the module adjust the parameter values automatically.
Before directly changing the PB, TI or TD register, you must set the Dynamic Auto-tuning
Enable (SELF) parameter to “0: disabled.” Otherwise, the dynamic auto-tuning function
will overwrite the modified value.
Table B3.12 Operation Parameters That Must be Set for PID Control
*1
Data Position Number
Symbol Description Unit
Data
Range Default
Value Attribute Stored
See
Also
Loop 1 Loop 2 Loop 3 Loop 4
201
401
601
801
1.SP
Set point
Industrial
unit
PRL to PRH
PRL
RW
C4.1
206
406
606
806
1.PB
Proportional band
%
1 to 9999 (0.1 to 999.9%)
50
RW
C6.2
207
407
607
807
1.TI
Integral time
Second
0: OFF
1 to 6000 (1 to 6000 s)
240
RW
C6.3
208
408
608
808
1.TD
Derivative time
Second
60
RW
C6.4
*1
To switch between PID parameter groups, see Section C4, "SP-related Functions."
You need to execute a specific procedure every time to update stored set point values.
Otherwise, stored set points will not be updated so the parameters revert to their last
stored values whenever the module is turned off and then on again. For details, see
Section B2.4, "How to Back up SP Values to EEPROM."
Set the PID control parameters PB, TI, and TD in Table B3.12 to appropriate values. To
set these parameters automatically with the auto-tuning function, first define the set point,
and then start the auto-tuning function as described below. Let us assume that the set
point to be used is 1.SP.
CAUTION
CAUTION
Содержание F3CU04-0S
Страница 2: ...Blank Page...
Страница 18: ...Blank Page...
Страница 32: ...Blank Page...
Страница 34: ...Blank Page...
Страница 50: ...Blank Page...
Страница 90: ...Blank Page...
Страница 97: ...B3 7 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 2 Sample Program for Setting Controller Parameters 2 2...
Страница 100: ...B3 10 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 3 Sample Program for Setting I O Parameters 2 3...
Страница 101: ...B3 11 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 3 Sample Program for Setting I O Parameters 3 3...
Страница 110: ...B4 2 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 2 5...
Страница 111: ...B4 3 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 3 5...
Страница 112: ...B4 4 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 4 5...
Страница 113: ...B4 5 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 5 5...
Страница 118: ...Blank Page...
Страница 130: ...Blank Page...
Страница 204: ...Blank Page...
Страница 215: ...C8 1 IM 34M06H62 02E 2nd Edition June 2008 00 C8 Alarm Function This chapter describes the alarm function of the module...
Страница 222: ...Blank Page...
Страница 224: ...Blank Page...
Страница 228: ...Blank Page...
Страница 230: ...Blank Page...
Страница 232: ...Blank Page...
Страница 234: ...Blank Page...
Страница 240: ...Blank Page...
Страница 242: ...Blank Page...
Страница 254: ...Blank Page...
Страница 258: ...Blank Page...
Страница 260: ...Blank Page...