C3-6
IM 34M06H62-02E
2nd Edition : June 2008-00
Table C3.3 Input Type Selection (2/2) (SW1-1 = ON)
Input Type
Instrument Range
Input Type
Selector Switch
*2
Software
Setting
Input Range
*1
Default
Allowable Range
SW5 SW1-4 SW1-3
IN
*3
RL
RH
DEC.P
RL
RH
Software setting
*4
0
OFF
X
Thermoco
uple
K
-328.0 to 2498.0
F 1
OFF
OFF
1 ($01)
-3280
24980
1 -4540
24980
ON 33
($21)
-328
2498
0 -454
2498
-328.0 to 1832.0
F 2
OFF
2 ($02)
-3280
18320
1 -4540
24980
ON 34
($22)
-328
1832
0 -454
2498
-328.0 to 932.0
F 3
OFF
3 ($03)
-3280
9320
1 -3280
9320
ON 35
($23)
-328
932
0 -328
932
J
-328.0 to 2192.0
F 4
OFF
4 ($04)
-3280
21920
1 -3280
21920
ON 36
($24)
-328
2192
0 -328
2192
-328.0 to 932.0
F 5
OFF
5 ($05)
-3280
9320
1 -3280
9320
ON 37
($25)
-328
932
0 -328
932
T
-454.0 to 752.0
F 6
OFF
6 ($06)
-4540
7520
1 -4540
7520
ON 38
($26)
-454
752
0 -454
752
B
32 to 2912
F 7
OFF
7 ($07)
32
2912
0
32
3272
ON 39
($27)
32
2912
0 32
3272
S
32 to 2912
F 8
OFF
8 ($08)
32
2912
0
32
3092
ON 40
($28)
32
2912
0 32
3092
R
32 to 2912
F 9
OFF
9 ($09)
32
2912
0
32
3092
ON 41
($29)
32
2912
0 32
3092
N
-328.0 to 2372.0
F A
OFF
10 ($0A)
-3280
23720
1 -3280
23720
ON 42
($2A)
-328
2372
0 -328
2372
E
-454.0 to 1832.0
F B
OFF
11 ($0B)
-4540
18320
1 -4540
18320
ON 43
($2B)
-454
1832
0 -454
1832
L
-328.0 to 1652.0
F C
OFF
12 ($0C)
-3280
16520
1 -3280
16520
ON 44
($2C)
-328
1652
0 -328
1652
U
-328.0 to 752.0
F D
OFF
13 ($0D)
-3280
7520
1 -3280
7520
ON 45
($2D)
-328
752
0 -328
752
W
32 to 2912
F E
OFF
14 ($0E)
32
2912
0
32
4172
ON 46
($2E)
32
2912
0
32
4172
Platinel 2
32.0 to 2534.0
F F
OFF
15 ($0F)
320
25340
1
320
25340
ON 47
($2F)
32
2534
0 32
2534
RT
D
JPt100
-328.0 to 932.0
F 0
ON
OFF
16 ($10)
-3280
9320
1 -3280
9320
ON 48
($30)
-328
932
0 -328
932
-328.0 to 392.0
F 1
OFF
17 ($11)
-3280
3920
1 -3280
3920
ON 49
($31)
-328
392
0 -328
392
32.0 to 572.0
F 2
OFF
18 ($12)
320
5720
1
320
5720
ON 50
($32)
32
572
0 32
572
32.0 to 302.0
F 3
OFF
19 ($13)
320
3020
1
320
3020
ON 51
($33)
32
302
0 32
302
Pt100
-328.0 to 1562.0
F 4
OFF
20 ($14)
-3280
15620
1 -3280
15620
ON 52
($34)
-328
1562
0 -328
1562
-328.0 to 932.0
F 5
OFF
21 ($15)
-3280
9320
1 -3280
9320
ON 53
($35)
-328
932
0 -328
932
-328.0 to 392.0
F 6
OFF
22 ($16)
-3280
3920
1 -3280
3920
ON 54
($36)
-328
392
0 -328
392
32.0 to 572.0
F 7
OFF
23 ($17)
320
5720
1
320
5720
ON 55
($37)
32
572
0 32
572
32.0 to 302.0
F 8
OFF
24 ($18)
320
3020
1
320
3020
ON 56
($38)
32
302
0 32
302
DC vo
ltage
0-10mV
0.00 to 10.00 mV
9
ON
X
25
($19)
0
1000 2 0
1000
0-100mV 0.0 to 100.0 mV
A
26 ($1A)
0
1000
1
0
1000
0-1V
0.000 to 1.000 V
B
27 ($1B)
0
1000
3
0
1000
0-5V
0.000 to 5.000 V
D
29 ($1D)
0
5000
3
0
5000
1-5V
1.000 to 5.000 V
E
30 ($1E)
1000
5000
3
1000
5000
0-10V
0.00
to10.00
V F
31
($1F)
0
1000 2 0
1000
*1: For thermocouples K, B, S, R, and W, the upper and lower input range limits may exceed their default values.
*2: Data stored in the internal memory is initialized to the hardware switch values when power is turned on. An ‘X’ symbol in the SW1-3
column indicates that the switch setting is ignored.
*3: “Software Setting” refers to values stored in data register IN. Any value not listed here is ignored.
*4: This is the factory setting. When ‘set by software’ is selected, the initial value of data register IN is ‘I: Thermocouple K’.
Содержание F3CU04-0S
Страница 2: ...Blank Page...
Страница 18: ...Blank Page...
Страница 32: ...Blank Page...
Страница 34: ...Blank Page...
Страница 50: ...Blank Page...
Страница 90: ...Blank Page...
Страница 97: ...B3 7 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 2 Sample Program for Setting Controller Parameters 2 2...
Страница 100: ...B3 10 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 3 Sample Program for Setting I O Parameters 2 3...
Страница 101: ...B3 11 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 3 Sample Program for Setting I O Parameters 3 3...
Страница 110: ...B4 2 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 2 5...
Страница 111: ...B4 3 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 3 5...
Страница 112: ...B4 4 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 4 5...
Страница 113: ...B4 5 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 5 5...
Страница 118: ...Blank Page...
Страница 130: ...Blank Page...
Страница 204: ...Blank Page...
Страница 215: ...C8 1 IM 34M06H62 02E 2nd Edition June 2008 00 C8 Alarm Function This chapter describes the alarm function of the module...
Страница 222: ...Blank Page...
Страница 224: ...Blank Page...
Страница 228: ...Blank Page...
Страница 230: ...Blank Page...
Страница 232: ...Blank Page...
Страница 234: ...Blank Page...
Страница 240: ...Blank Page...
Страница 242: ...Blank Page...
Страница 254: ...Blank Page...
Страница 258: ...Blank Page...
Страница 260: ...Blank Page...