C2-12
IM 34M06H62-02E
2nd Edition : June 2008-00
Rate-of-change Limit
The rate-of-change limit prevents drastic changes in the output by defining the maximum
rate of change allowed in the control output. This function is useful for protecting a
controlled load or machine.
For example, supposing that the rate-of-change is set to 2% per second, even if the PID
computation result changes instantly from 0 to 100%, the actual output changes linearly
from 0 to 100% over a duration of 50 s.
Figure C2.6 Rate-of-change Limit
Table C2.12 Rate-of-change Limit Parameter
Data Position Number
Symbol Description Unit
Data Range
Default
Value Attribute Stored
Loop 1 Loop 2 Loop 3 Loop 4
193 393 593 793 MVR
Rate-of-change
limit %/s
0: OFF
1 to 1000 (0.1 to 100.0% per second)
0 RW
The rate-of-change limit is disabled in the following situations:
-
When the Run/Stop Selection is set to Stop
-
When the Automatic/manual/cascade Selection is set to Manual
-
If burnout or AD converter error is detected when the Automatic/manual/cascade
Selection is set to Automatic (see Section C10, "Self-diagnosis Function")
-
When heating/cooling PID control is selected.
Содержание F3CU04-0S
Страница 2: ...Blank Page...
Страница 18: ...Blank Page...
Страница 32: ...Blank Page...
Страница 34: ...Blank Page...
Страница 50: ...Blank Page...
Страница 90: ...Blank Page...
Страница 97: ...B3 7 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 2 Sample Program for Setting Controller Parameters 2 2...
Страница 100: ...B3 10 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 3 Sample Program for Setting I O Parameters 2 3...
Страница 101: ...B3 11 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 3 Sample Program for Setting I O Parameters 3 3...
Страница 110: ...B4 2 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 2 5...
Страница 111: ...B4 3 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 3 5...
Страница 112: ...B4 4 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 4 5...
Страница 113: ...B4 5 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 5 5...
Страница 118: ...Blank Page...
Страница 130: ...Blank Page...
Страница 204: ...Blank Page...
Страница 215: ...C8 1 IM 34M06H62 02E 2nd Edition June 2008 00 C8 Alarm Function This chapter describes the alarm function of the module...
Страница 222: ...Blank Page...
Страница 224: ...Blank Page...
Страница 228: ...Blank Page...
Страница 230: ...Blank Page...
Страница 232: ...Blank Page...
Страница 234: ...Blank Page...
Страница 240: ...Blank Page...
Страница 242: ...Blank Page...
Страница 254: ...Blank Page...
Страница 258: ...Blank Page...
Страница 260: ...Blank Page...