C1-1
IM 34M06H62-02E
2nd Edition : June 2008-00
C1. Controller Mode
The controller mode defines the interdependency of the four controller loops of the
module. When the controller mode is set to single loop, each controller operates
independently. When the controller mode is set to cascade control or two-input
changeover control, a pair of controller loops 1 and 2, or a pair of controller loops 3
and 4, cooperate to function like a single controller. For an overview on control
modes, see Section B3.1.3, "Controller Mode."
The controller mode selection uses the MD12 or MD34 register for a pair of
controller loops 1 and 2 or a pair of controller loops 3 and 4 respectively.
Table C1.1 Parameters Related to Controller Mode
Data Position Number
Symbol Description Unit
Data
Range
Default
Value Attribute Stored
Loop1 Loop2 Loop3 Loop4
83
MD12
Controller mode
None
0: Two single loops
1: Two-input changeover control
2: Cascade control
3: One single loop
(odd-numbered loops are disabled)
4: Both loops are disabled
0 RW
84 MD34
None
Table C1.2 How Controller Loops are Used according to the Controller Mode Setting
Symbol Description
How Loops are Used
Odd-numbered
Loop
(1 or 3)
Even-numbered Loop
(2 or 4)
MD12
MD34
Controller Mode
0: Two single loops
Single loop
Single loop
1: Two-input changeover control
Cooling input
*1
Heating
input
2: Cascade control
Primary loop of cascade
Secondary loop of cascade
3: One single loop
(odd-numbered loops are disabled)
Disabled Single
loop
4: Both loops are disabled. Disabled
Disabled
*1
Only the input side of the loop is used.
For details on Single Loop, Cascade Control, and Two-input Changeover control
modes, see Sections C1.1, "Single Loop," C1.2, "Cascade Control," and C1.3,
"Two-input Changeover Control" respectively. For details on how to disable the
controller functions, see Section C1.4, "Disabled Mode."
The MD12 and MD34 (Controller Mode) registers are controller parameters. Changing a
controller parameter normally reverts all parameters of the module to their default values.
However, switching between the values 0, 3 and 4 (between the disabled-mode and
single-loop settings) of MD12 or MD34 does not initialize the parameters.
The Controller Mode settings must be enabled to take effect. For details on how to
enable settings, see Section B2.3, "How to Enable Settings."
Содержание F3CU04-0S
Страница 2: ...Blank Page...
Страница 18: ...Blank Page...
Страница 32: ...Blank Page...
Страница 34: ...Blank Page...
Страница 50: ...Blank Page...
Страница 90: ...Blank Page...
Страница 97: ...B3 7 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 2 Sample Program for Setting Controller Parameters 2 2...
Страница 100: ...B3 10 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 3 Sample Program for Setting I O Parameters 2 3...
Страница 101: ...B3 11 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 3 Sample Program for Setting I O Parameters 3 3...
Страница 110: ...B4 2 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 2 5...
Страница 111: ...B4 3 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 3 5...
Страница 112: ...B4 4 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 4 5...
Страница 113: ...B4 5 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 5 5...
Страница 118: ...Blank Page...
Страница 130: ...Blank Page...
Страница 204: ...Blank Page...
Страница 215: ...C8 1 IM 34M06H62 02E 2nd Edition June 2008 00 C8 Alarm Function This chapter describes the alarm function of the module...
Страница 222: ...Blank Page...
Страница 224: ...Blank Page...
Страница 228: ...Blank Page...
Страница 230: ...Blank Page...
Страница 232: ...Blank Page...
Страница 234: ...Blank Page...
Страница 240: ...Blank Page...
Страница 242: ...Blank Page...
Страница 254: ...Blank Page...
Страница 258: ...Blank Page...
Страница 260: ...Blank Page...