C2-21
IM 34M06H62-02E
2nd Edition : June 2008-00
C2.4.4 Heating/Cooling ON/OFF Control
In Heating/Cooling ON/OFF Control, the module turns on or turns off the heating or
cooling output depending on the deviation between the control set point (CSP) and the
PV. To select Heating/Cooling ON/OFF Control, set the Control Type Selection (OT)
parameter to 3. For details, see Section C2.1, "Control Type Selection."
The value of the heating or cooling output is either 0% or 100%.
You can specify a dead band around the CSP for turning on the heating and cooling
outputs.
You can also specify a hysteresis for on/off or off/on transitions in the heating or cooling
output.
Conditions for turning on and turning off heating control output
On condition: (CSP - PV)
DB/2 + HYS/2
Off condition: (CSP - PV) < DB/2 - HYS/2
Conditions for turning on and turning off cooling control output
On condition: (CSP - PV)
-(DB/2 + HYS.C/2)
Off condition: (CSP - PV) > -(DB/2 - HYS.C/2)
Figure C2.12 Heating/Cooling ON/OFF Control (with positive dead band)
Figure C2.13 Heating/Cooling ON/OFF Control (with negative dead band)
Содержание F3CU04-0S
Страница 2: ...Blank Page...
Страница 18: ...Blank Page...
Страница 32: ...Blank Page...
Страница 34: ...Blank Page...
Страница 50: ...Blank Page...
Страница 90: ...Blank Page...
Страница 97: ...B3 7 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 2 Sample Program for Setting Controller Parameters 2 2...
Страница 100: ...B3 10 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 3 Sample Program for Setting I O Parameters 2 3...
Страница 101: ...B3 11 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B3 3 Sample Program for Setting I O Parameters 3 3...
Страница 110: ...B4 2 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 2 5...
Страница 111: ...B4 3 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 3 5...
Страница 112: ...B4 4 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 4 5...
Страница 113: ...B4 5 IM 34M06H62 02E 2nd Edition June 2008 00 Figure B4 1 Sample Program Component for Setting Setup Parameters 5 5...
Страница 118: ...Blank Page...
Страница 130: ...Blank Page...
Страница 204: ...Blank Page...
Страница 215: ...C8 1 IM 34M06H62 02E 2nd Edition June 2008 00 C8 Alarm Function This chapter describes the alarm function of the module...
Страница 222: ...Blank Page...
Страница 224: ...Blank Page...
Страница 228: ...Blank Page...
Страница 230: ...Blank Page...
Страница 232: ...Blank Page...
Страница 234: ...Blank Page...
Страница 240: ...Blank Page...
Страница 242: ...Blank Page...
Страница 254: ...Blank Page...
Страница 258: ...Blank Page...
Страница 260: ...Blank Page...