L4-04
L4-04
Frequency
reference
Speed Agree 2
ON
OFF
ON
OFF
Output Frequency
Figure 1.46 Speed Agree 2 Time Chart
Refer to L4-03, L4-04: Speed Agree Detection Level and Detection Width (+/-) on page 116
Setting 14: User-Set Speed Agree 2 (f
ref
/f
set
Agree 2)
The output closes when the actual output frequency and the frequency reference are within the speed agree width (L4-04) of
the programmed speed agree level (L4-03).
Status
Description
Open
Output frequency and frequency reference are both outside the range of L4-03 ±L4-04.
Closed
Output frequency and the frequency reference are both within the range of L4-03 ±L4-04.
Note:
The detection level L4-03 is a signed value; detection works in the specified direction only.
Frequency reference
+
L4-04
Frequency reference – L4-04
L4-03
L4-03
+
L4-04
L4-03 – L4-04
Frequency reference
0 Hz
OFF
OFF
ON
ON
Frequency reference
During
Forward
Output frequency
Output frequency
User Set
Speed Agree 2
Figure 1.47 User-Set Speed Agree 2 Example with a Positive L3-04 Value
Refer to L4-03, L4-04: Speed Agree Detection Level and Detection Width (+/-) on page 116
Setting 15: Frequency Detection 3
The output opens when the output frequency rises above the detection level set in L4-03 plus the detection with set in L4-04.
The terminal remains open until the output frequency falls below the level set in L4-03. The detection level L4-03 is a signed
value; detection works in the specified direction only.
Status
Description
Open
Output frequency exceeded L4-03 plus L4-04.
Closed
Output frequency is below L4-03 or has not exceeded L4-03 plus L4-04.
1.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
93
1
Parameter Details