Setting
Function
Page
6
Drive Ready
7
During Power Supply Voltage Fault
8
During Baseblock (N.O.)
9
Frequency Reference Source
A
Run Command Source
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
E
Fault
F
Through Mode
10
Minor Fault
11
Fault Reset Command Active
12
Timer Output
13
Speed Agree 2
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
1B
During Baseblock (N.C.)
1E
Restart Enabled
1F
Motor Overload Alarm (oL1)
20
Drive Overheat Pre-Alarm (oH)
2F
Maintenance Period
37
During Frequency Output
38
Drive Enabled
39
Power Consumption Pulse Output
Setting
Function
Page
3A
Regenerated Power Pulse Output
3D
During Speed Search
3E
PID Feedback Low
3F
PID Feedback High
4C
During Fast Stop
4D
oH Pre-Alarm Time Limit
50
Waiting for Run
51
Sequence Timer 1 Active
52
Sequence Timer 2 Active
53
Sequence Timer 3 Active
54
Sequence Timer 41 Active
58
Underload Detection
60
Internal Cooling Fan Alarm
62
MEMOBUS Register 1
63
MEMOBUS Register 2
64
During Commercial Power Operation
AF
BP Drive Relay Contact
B0
BP Bypass Relay Contact
B1
BP BAS Interlock Relay Contact
B2
BAS Interlock Relay Contact
B3
Secondary PI Feedback Low
B4
Secondary PI Feedback High
B5
Relay Operator Control
B6
Drive Overheat Alarm 2
100 to 1B6 Functions 0 to B6 with Inverse Output
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status
Description
Open
Drive is stopped.
Closed
A Run command is input or the drive is in deceleration or DC injection.
ON
ON
OFF
OFF
ON
OFF
Run command
Baseblock
command
Output
frequency
During Run
Figure 1.40 During Run Time Chart
Setting 1: Zero Speed
Terminal closes when the output frequency falls below the minimum output frequency set to E1-09 or b2-01.
Status
Description
Open
Output frequency is above the minimum output frequency set to E1-09 or b2-01
Closed
Output frequency is less than the minimum output frequency set to E1-09 or b2-01
1.7 H: Terminal Functions
88
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual