n
T2-14: PM Motor Induced Voltage Constant (Ke)
Enter the motor induced voltage constant (Ke).
No.
Name
Setting Range
Default
T2-14
PM Motor Induced Voltage Constant (Ke)
0.0 to 2000.0
Determined by T2-02
n
T2-15: Pull-In Current Level for PM Motor Tuning
Sets the amount of pull-in current. Set as a percentage of the motor rated current.
No.
Name
Setting Range
Default
T2-15
Pull-In Current Level for PM Motor Tuning
0 to 120%
30%
1.12 T: Motor Tuning
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
163
1
Parameter Details