H2: Multi-Function Digital Outputs
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H2-01
(040B)
Terminal M1-M2
function selection
(relay)
M1-M2 Func Sel
Refer to H2 Multi-Function Digital Output Settings on pages
for descriptions of setting values.
Default: 0
Range: 0 to 1B6
H2-02
(040C)
Terminal M3-M4
function selection
(relay)
M3/M4 Func Sel
Default: 1
Range: 0 to 1B6
H2-03
(040D)
Terminal MD-ME-MF
function selection
(relay)
MD/ME/MF FuncSel
Default: 2
Range: 0 to 1B6
H2-06
(0437)
Power Consumption
Output Unit Selection
Pwr Mon Unit Sel
Sets the units for the output signal when Power Consumption
Pulse Output or Regenerated Power Pulse Output are selected
as the digital output (H2-01, H2-02, or H2-03 = 39 or 3A).
0: 0.1 kWh units
<1>
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
Default: 1
Range: 0 to 4
H2-07
(0B3A)
MEMOBUS Register 1
Address Select
MFDO Regs1 Addr
Sets the addresses of the MEMOBUS/Modbus registers from
which data will be sent to contact outputs 62 and 162.
Default: 1
Range: 1 to
1FFFH
H2-08
(0B3B)
MEMOBUS Register 1
Bit Select
MFDO Regs1 Bit
Sets the bits for the MEMOBUS/Modbus registers from which
data will be sent to contact outputs 62 and 162.
Default: 0
Range: 0 to
FFFFH
H2-09
(0B3C)
MEMOBUS Register 2
Address Select
MFDO Regs2 Addr
Sets the addresses of the MEMOBUS/Modbus registers from
which data will be sent to contact outputs 63 and 163.
Default: 1
Range: 1 to
1FFFH
H2-10
(0B3D)
MEMOBUS Register 2
Bit Select
MFDO Regs2 Bit
Sets the bits for the MEMOBUS/Modbus registers from which
data will be sent to contact outputs 63 and 163.
Default: 0
Range: 0 to
FFFFH
<1> Available in drive software versions PRG: 6113 and later.
H2 Multi-Function Digital Output Settings
H2-
oo
Setting
Function
LCD Display
Description
Page
0
During run
During RUN 1
Closed: A Run command is active or voltage is output.
1
Zero speed
Zero Speed
Open: Output frequency is above the minimum output frequency set in E1-09.
Closed: Output frequency is below the minimum output frequency set in E1-09.
2
Speed agree 1
Fref/Fout Agree1
Closed: Output frequency equals the speed reference (plus or minus the hysteresis
set to L4-02).
3
User-set speed agree 1
Fref/Set Agree 1
Closed: Output frequency and speed reference equal L4-01 (plus or minus the
hysteresis set to L4-02).
4
Frequency detection 1
Freq Detect 1
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
determined by L4-02.
5
Frequency detection 2
Freq Detect 2
Closed: Output frequency is greater than or equal to the value in L4-01 with
hysteresis determined by L4-02.
6
Drive ready
Drive Ready
Closed: Power up is complete and the drive is ready to accept a Run command.
7
During Power Supply
Voltage Fault
DC Bus Undervolt
Closed: One of the following faults will occur: AUv (Power Supply Undervoltage),
Uv (Undervoltage). or Fdv (Power Supply Frequency Fault).
8
During baseblock (N.O.) BaseBlk 1
Closed: Drive has entered the baseblock state (no output voltage).
9
Frequency reference
source
Ref Source
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01).
Closed: HOA keypad supplies the frequency reference.
A
Run command source
Run Cmd Source
Open: External Reference 1 or 2 supplies the Run command (set in b1-02).
Closed: HOA keypad supplies the Run command.
B
Torque detection 1
(N.O.)
Trq Det 1 N.O.
Closed: An overtorque or undertorque situation has been detected.
C
Frequency reference loss Loss of Ref
Closed: Analog frequency reference has been lost.
E
Fault
Fault
Closed: Fault occurred.
A.9 H Parameters: Multi-Function Terminals
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
221