b5-11
(01AF)
PID Output Reverse
Selection
Output Rev Sel
0: 0 limit
1: Reverse
0: Negative PID output triggers zero limit.
1: Rotation direction reverses with negative PID output.
Note:
When using setting 1, make sure reverse
operation is permitted by b1-04.
Default: 0
Range: 0, 1
b5-12
(01B0)
PID Feedback Loss
Detection Selection
Fb loss Det Sel
0: Disabled
1: Alarm @ PID Enbl
2: Fault @ PID Enbl
3: DO Only@PID
Enbl
4: Alarm – Always
5: Fault – Alwaysl
0: Digital Output Only
(Remains active when PID is disabled by digital input)
1: Alarm output, drive continues operation (Remains active
when PID is disabled by digital input)
2: Fault output, drive output is shut off (Remains active when
PID is disabled by digital input)
3: Digital output only. No detection when PID is disabled by
digital input.
4: Alarm detection. No detection when PID is disabled by digital
input.
5: Fault detection. No detection when PID is disabled by digital
input.
Default: 0
Range: 0 to 5
b5-13
(01B1)
PID Feedback Loss
Detection Level
Fb loss Det Lvl
Sets the PID feedback loss detection level as a percentage of the
maximum output frequency.
Default: 0%
Min.: 0
Max.: 100
b5-14
(01B2)
PID Feedback Loss
Detection Time
Fb loss Det Time
Sets a delay time for PID feedback loss.
Default: 1.0 s
Min.: 0.0
Max.: 25.5
b5-15
(01B3)
PID Sleep Function Start
Level
PID Sleep Level
Sets the frequency level that triggers the sleep/snooze function. Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
b5-16
(01B4) PID Sleep Delay Time
PID Sleep Time
Sets a delay time before the sleep/snooze function is triggered. Default: 0.0 s
Min.: 0.0
Max.: 25.5
b5-17
(01B5) PID Accel/Decel Time PID Acc/Dec Time
Sets the acceleration and deceleration time to PID setpoint.
Default: 0.0 s
Min.: 0.0
Max.: 6000.0
b5-18
(01DC) PID Setpoint Selection
PID Setpoint Sel
0: Disabled
1: Enabled
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
b5-19
(01DD) PID Setpoint Value
PID Setpoint
Sets the PID target value when b5-18 = 1. Set as a percentage
of the maximum output frequency.
Default: 0.00%
Min.: 0.00
Max.: 100.00
<1>
b5-20
(01E2) PID Setpoint Scaling
PID Disp Scaling
0: 0.01Hz units
1: 0.01% units
2: r/min
3: User Units
0: 0.01 Hz units
1: 0.01% units (100% = max output frequency)
2: r/min (number of motor poles must entered)
3: User-set (set scaling to b5-38 and b5-39)
Default: 1
Range: 0 to 3
b5-21
(01E3) PID Sleep Input Source
PID Sleep Ref
0: PID Setpoint
1: Frequency Ref
2: Snooze Func
Input source selection for Sleep Function mode.
0: PID Setpoint
1: SFS Input
2: Snooze
Default: 1
Range: 0 to 2
b5-22
(01E4) PID Snooze Level
Snooze Level
Sets the PID Snooze Function start level as a percentage of the
maximum frequency.
Default: 0%
Min.: 0
Max.: 100
b5-23
(01E5) PID Snooze Delay Time Snooze DelayTime
Sets the PID Snooze Function delay time in seconds.
Default: 0s
Min.: 0
Max.: 2600
b5-24
(01E6)
PID Snooze
Deactivation Level
SnoozeRestartLvl
When the PID feedback level drops below this level, the drive
returns to normal operation. Set as a percentage of the maximum
frequency.
Default: 0%
Min.: 0
Max.: 100
b5-25
(01E7)
PID Setpoint Boost
Setting
SetpointBoostLvl
Temporarily increases the PID setpoint to create an overshoot
of the intended PID setpoint.
Default: 0%
Min.: 0
Max.: 100
b5-26
(01E8)
PID Maximum Boost
Time
SetpointBoostTim
Sets the maximum boost time when PID feedback does not
reach boost level.
The Snooze Function starts when the PID feedback exceeds the
boost setting level or when the boost time expires.
Default: 0s
Min.: 0
Max.: 2600
A.4 b: Application
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
199