No.
Name
Unit
Default Settings
–
Drive Model
–
4
o
0034
4
o
0040
4
o
0052
4
o
0065
o2-04
Drive Model Selection
Hex.
9C
9D
9E
9F
E2-11
Motor Rated Output
kW (HP)
18.5 (25)
22 (30)
30 (40)
37 (50)
E2-10
Motor Iron Loss for Torque Compensation
W
440
508
586
750
E5-01
Motor Code Selection (for PM Motors)
Hex.
123D
123E
123F
1240
L2-02
Momentary Power Loss Ride-Thru Time
s
1
1
1
1.1
L2-03
Momentary Power Loss Minimum Baseblock
Time
s
0.6
0.6
0.6
0.6
L2-04
Momentary Power Loss Voltage Recovery
Time
s
300
300
300
300
L8-02
Overheat Alarm Level
°C
130
130
130
130
L8-35
Installation Method Selection
–
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
Table A.11 400 V Class Drives Default Settings by Drive Model Selection
No.
Name
Unit
Default Settings
–
Drive Model
–
4
o
0077
4
o
0096
4
o
0124
4
o
0156
o2-04
Drive Model Selection
Hex.
A1
A2
A3
A4
E2-11
Motor Rated Output
kW (HP)
45 (60)
55 (75)
75 (100)
90 (125)
b3-04
V/f Gain during Speed Search
%
100
100
80
60
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.8
b8-04
Energy Saving Coefficient Value
–
76.32
71.56
67.2
46.2
C6-02
Carrier Frequency Selection
–
1
1
1
1
E2-01
Motor Rated Current
A
65.6
79.7
95
130
E2-02
Motor Rated Slip
Hz
1.33
1.6
1.46
1.39
E2-03
Motor No-Load Current
A
19.1
22
24
36
E2-05
Motor Line-to-Line Resistance
Ω
0.155
0.122
0.088
0.092
E2-06
Motor Leakage Inductance
%
18.8
19.9
20
20
E2-10
Motor Iron Loss for Torque Compensation
W
925
1125
1260
1600
E5-01
Motor Code Selection (for PM Motors)
Hex.
1242
1243
1244
1245
L2-02
Momentary Power Loss Ride-Thru Time
s
1.1
1.2
1.2
1.3
L2-03
Momentary Power Loss Minimum Baseblock
Time
s
0.6
0.6
1
1
L2-04
Momentary Power Loss Voltage Recovery
Time
s
300
300
300
300
L8-02
Overheat Alarm Level
°C
130
130
130
130
L8-35
Installation Method Selection
–
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
10
10
10
30
Table A.12 400 V Class Drives Default Settings by Drive Model Selection
No.
Name
Unit
Default Settings
–
Drive Model
–
4
o
0180
4
o
0216
4
o
0240
4
o
0302
4
o
0361
4
o
0414
o2-04
Drive Model Selection
Hex.
A5
A6
A7
A8
A9
AA
E2-11
Motor Rated Output
kW (HP)
110 (150)
132 (175)
150 (200)
185 (250)
220 (300)
260 (350)
b3-04
V/f Gain during Speed Search
%
60
60
60
60
60
60
b3-06
Output Current 1 during Speed Search
–
0.7
0.7
0.7
0.7
0.7
0.7
b3-08
Current Control Gain during Speed
Search
(Speed Estimation Type)
–
0.8
0.8
0.8
0.8
0.8
0.8
b8-04
Energy Saving Coefficient Value
–
38.91
36.23
32.79
30.13
30.57
27.13
C6-02
Carrier Frequency Selection
–
1
1
1
1
1
1
A.18 Defaults by Drive Model
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
261
A
Parameter List