T2: PM Motor Auto-Tuning
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
T2-01
(0750)
PM Motor Auto-Tuning
Mode Selection
PM Tuning Mode
0: Standard Tuning
1: Tune-No Rotate
2: Term Resistance
14: PM Rotation
Tune
OLV/PM
OLV/PM
0: PM Motor Parameter Settings
1: PM Stationary Auto-Tuning
2: PM Stationary Auto-Tuning for Stator Resistance
14: PM Rotational Auto-Tuning
Default: 0
Range: 0 to 2;
14
T2-02
(0751)
PM Motor Code
Selection
PM Mtr Code Sel
OLV/PM
OLV/PM
Enter the motor code when using a Yaskawa PM motor. After
entering the motor code, the drive automatically sets parameters
T2-03 through T2-09. Set parameters T2-10 to T2-14 according
the motor nameplate or the motor test report. When using a motor
without a supported motor code or a non-Yaskawa motor, set
FFFF and adjust the other T2 parameters according to the motor
nameplate or the motor test report.
Default:
<1>
Min: 0000
Max: FFFF
T2-03
(0752)
PM Motor Type
PM Motor Type
0: IPM motor
1: SPM motor
OLV/PM
OLV/PM
0: IPM motor
1: SPM motor
Default: 1
Range: 0, 1
T2-04
(0730)
PM Motor Rated Power Mtr Rated Power
OLV/PM
OLV/PM
Sets the motor rated power.
Note:
Use the following formula to convert horsepower
into kilowatts:
1HP = 0.746 kW.
Default:
<1>
Min.: 0.00 kW
Max.: 650.00
kW
T2-05
(0732)
PM Motor Rated
Voltage
Rated Voltage
OLV/PM
OLV/PM
Enter the motor rated voltage as indicated on the motor nameplate.
Default: 200.0
V
<2>
Min.: 0.0
Max.: 255.0
<2>
T2-06
(0733)
PM Motor Rated Current Rated Current
OLV/PM
OLV/PM
Enter the motor rated current as indicated on the motor nameplate.
Default:
<1>
Min.: 10% of
drive rated
current
Max.: 150% of
drive rated
current
T2-07
(0753)
PM Motor Base
Frequency
Base Frequency
OLV/PM
OLV/PM
Enter the motor base frequency as indicated on the motor
nameplate.
Default: 87.5
Hz
Min.: 0.0
Max.: 400.0
T2-08
(0734)
Number of PM Motor
Poles
Number of Poles
OLV/PM
OLV/PM
Enter the number of motor poles for the PM motor as indicated
on the motor nameplate.
Default: 6
Min.: 2
Max.: 48
T2-10
(0754)
PM Motor Stator
Resistance
Arm Resistance
OLV/PM
OLV/PM
Enter the rotor resistance for the PM motor as indicated on the
motor nameplate.
Default:
<3>
Min.: 0.000 Ω
Max.: 65.000 Ω
T2-11
(0735)
PM Motor d-Axis
Inductance
d-Axis Induct
OLV/PM
OLV/PM
Enter the d-axis inductance for the PM motor as indicated on the
motor nameplate.
Default:
<3>
Min.: 0.00 mH
Max.: 600.00
mH
T2-12
(0736)
PM Motor q-Axis
Inductance
q-Axis Induct
OLV/PM
OLV/PM
Enter the q-axis inductance for the PM motor as indicated on the
motor nameplate.
Default:
<3>
Min.: 0.00 mH
Max.: 600.00
mH
T2-13
(0755)
Induced Voltage
Constant Unit Selection
Iduct Volt Unit
0: mV/RPM
1: mV/(rad/sec)
OLV/PM
OLV/PM
0: mV/(r/min). E5-09 will automatically be set to 0.0, and E5-24
will be used.
1: mV/(rad/sec). E5-24 will automatically be set to 0.0, and E5-09
will be used.
Default: 1
Range: 0, 1
A.14 T: Motor Tuning
246
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual