![YASKAWA Z1000U Series Скачать руководство пользователя страница 214](http://html2.mh-extra.com/html/yaskawa/z1000u-series/z1000u-series_programming-manual_3226538214.webp)
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
F6-56
(03D7)
DeviceNet Speed
Scaling
Speed Scale
Sets the scaling factor for the speed monitor in DeviceNet.
Default: 0
Min.: -15
Max.: 15
F6-57
(03D8)
DeviceNet Current
Scaling
Current Scale
Sets the scaling factor for the output current monitor in
DeviceNet.
Default: 0
Min.: -15
Max.: 15
F6-58
(03D9)
DeviceNet Torque
Scaling
Torque Scale
Sets the scaling factor for the torque monitor in DeviceNet.
Default: 0
Min.: -15
Max.: 15
F6-59
(03DA)
DeviceNet Power
Scaling
Power Scale
Sets the scaling factor for the power monitor in DeviceNet.
Default: 0
Min.: -15
Max.: 15
F6-60
(03DB)
DeviceNet Voltage
Scaling
Voltage Scale
Sets the scaling factor for the voltage monitor in DeviceNet.
Default: 0
Min.: -15
Max.: 15
F6-61
(03DC) DeviceNet Time Scaling Time Scale
Sets the scaling factor for the time monitor in DeviceNet.
Default: 0
Min.: -15
Max.: 15
F6-62
(03DD)
DeviceNet Heartbeat
Interval
DN Heart Beat
Sets the heartbeat interval for DeviceNet communications.
Default: 0
Min.: 0
Max.: 10
F6-63
(03DE)
DeviceNet Network
MAC ID
DN MAC ID MEM
Saves and monitors settings 0 to 63 of F6-50 (DeviceNet MAC
Address).
Default: 63
Min.: 0
Max.: 63
F6-64 to
F6-71
(03DF to
03C8)
Reserved
–
Reserved for Dynamic I/O Assembly Parameters.
–
–
F6-72
(03DE)
PowerLink Node
Address
PowerLink NodeID
Reserved.
–
–
F7-01
(03E5)
<4>
<5>
<6>
IP Address 1
IP Address 1
Sets the most significant octet of network static IP address.
Default: 192
Min.: 0
Max.: 255
–
F7-02
(03E6)
<4>
<5>
<6>
IP Address 2
IP Address 2
Sets the second most significant octet of network static IP
address.
Default: 168
Min.: 0
Max.: 255
–
F7-03
(03E7)
<4>
<5>
<6>
IP Address 3
IP Address 3
Sets the third most significant octet of network static IP address.
Default: 1
Min.: 0
Max.: 255
–
F7-04
(03E8)
<4>
<5>
<6>
IP Address 4
IP Address 4
Sets the fourth most significant octet of network static IP
address.
Default: 20
Min.: 0
Max.: 255
–
F7-05
(03E9)
<6>
Subnet Mask 1
Subnet Mask 1
Sets the most significant octet of network static Subnet Mask.
Default: 255
Min.: 0
Max.: 255
–
F7-06
(03EA)
<6>
Subnet Mask 2
Subnet Mask 2
Sets the second most significant octet of network static Subnet
Mask.
Default: 255
Min.: 0
Max.: 255
–
F7-07
(03EB)
<6>
Subnet Mask 3
Subnet Mask 3
Sets the third most significant octet of network static Subnet
Mask.
Default: 255
Min.: 0
Max.: 255
–
F7-08
(03EC)
<6>
Subnet Mask 4
Subnet Mask 4
Sets the fourth most significant octet of network static Subnet
Mask.
Default: 0
Min.: 0
Max.: 255
–
F7-09
(03ED)
<6>
Gateway Address 1
Gateway IP Add 1
Sets the most significant octet of network Gateway address.
Default: 192
Min.: 0
Max.: 255
–
A.8 F: Option Settings
214
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual