![YASKAWA Z1000U Series Скачать руководство пользователя страница 260](http://html2.mh-extra.com/html/yaskawa/z1000u-series/z1000u-series_programming-manual_3226538260.webp)
No.
Name
Unit
Default Settings
–
Drive Model
–
2
o
0081
2
o
0104
2
o
0130
2
o
0154
2
o
0192
2
o
0248
o2-04
Drive Model Selection
Hex.
6F
70
72
73
74
75
E2-11
Motor Rated Output
kW (HP)
22 (30)
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
L2-04
Momentary Power Loss Voltage
Recovery Time
s
150
150
150
150
150
150
L8-02
Overheat Alarm Level
°C
130
130
130
130
130
130
L8-35
Installation Method Selection
–
0
0
0
0
0
0
L8-38
Carrier Frequency Reduction
Selection
–
1
1
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
10
Table A.9 400 V Class Drives Default Settings by Drive Model Selection
No.
Name
Unit
Default Settings
–
Drive Model
–
4
o
0011
4
o
0014
4
o
0021
4
o
0027
o2-04
Drive Model Selection
Hex.
95
97
99
9A
E2-11
Motor Rated Output
kW (HP)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
b3-04
V/f Gain during Speed Search
%
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.5
b8-04
Energy Saving Coefficient Value
–
245.8
189.5
145.38
140.88
C6-02
Carrier Frequency Selection
–
1
1
1
1
E2-01
Motor Rated Current
A
7
9.8
13.3
19.9
E2-02
Motor Rated Slip
Hz
2.7
1.5
1.3
1.7
E2-03
Motor No-Load Current
A
2.3
2.6
4
5.6
E2-05
Motor Line-to-Line Resistance
Ω
3.333
1.595
1.152
0.922
E2-06
Motor Leakage Inductance
%
19.3
18.2
15.5
19.6
E2-10
Motor Iron Loss for Torque Compensation
W
130
193
263
385
E5-01
Motor Code Selection (for PM Motors)
Hex.
1236
1238
123A
123B
L2-02
Momentary Power Loss Ride-Thru Time
s
0.6
0.7
0.8
0.9
L2-03
Momentary Power Loss Minimum Baseblock
Time
s
0.3
0.3
0.3
0.3
L2-04
Momentary Power Loss Voltage Recovery
Time
s
300
300
300
300
L8-02
Overheat Alarm Level
°C
130
130
130
130
L8-35
Installation Method Selection
–
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
Table A.10 400 V Class Drives Default Settings by Drive Model Selection
No.
Name
Unit
Default Settings
–
Drive Model
–
4
o
0034
4
o
0040
4
o
0052
4
o
0065
o2-04
Drive Model Selection
Hex.
9C
9D
9E
9F
E2-11
Motor Rated Output
kW (HP)
18.5 (25)
22 (30)
30 (40)
37 (50)
b3-04
V/f Gain during Speed Search
%
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.5
b8-04
Energy Saving Coefficient Value
–
126.26
115.74
103.58
92.54
C6-02
Carrier Frequency Selection
–
1
1
1
1
E2-01
Motor Rated Current
A
26.5
32.9
38.6
52.3
E2-02
Motor Rated Slip
Hz
1.6
1.67
1.7
1.8
E2-03
Motor No-Load Current
A
7.6
7.8
9.2
10.9
E2-05
Motor Line-to-Line Resistance
Ω
0.55
0.403
0.316
0.269
E2-06
Motor Leakage Inductance
%
17.2
20.1
23.5
20.7
A.18 Defaults by Drive Model
260
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual