No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
F6-32
(03CD)
PROFIBUS-DP Data
Format Selection
PB Map Select
0: PPO Type
1: Conventional
0: PPO Type
1: Conventional
Default: 0
Range: 0, 1
F6-35
(03D0)
CANopen Node ID
Selection
CO Node Address
Sets the node address.
Default: 0
Min.: 0
Max.: 126
F6-36
(03D1)
CANopen
Communication Speed
CO Baud Rate
0: Auto Detect
1: 10 kbps
2: 20 kbps
3: 50 kbps
4: 125 kbps
5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1Mbps
0: Auto-detection
1: 10 kbps
2: 20 kbps
3: 50 kbps
4: 125 kbps
5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1 Mbps
Default: 6
Range: 0 to 8
F6-40
(03D5)
CompoNet Node
Address
CN Node Adress
Reserved.
–
–
F6-41
(03D6)
CompoNet
Communication Speed
CN Baud Rate
Reserved.
–
–
F6-45
(02FB) BACnet Node Address BAC Node Address
Sets BACnet physical node address.
Default: 1
Min.: 0
Max.: 127
F6-46
(02FC) BACnet Baud Rate
BAC Baud Rate
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19.2 kbps
5: 38.4 kbps
6: 57.6 kbps
7: 76.8 kbps
8: 115.2 kbps
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 76800
8: 115200
Default: 3
Range: 0 to 8
F6-47
(02FD) Rx to Tx Wait Time
Rx to Tx Wait T
Sets the wait time between receiving and sending for BACnet.
Default: 5 ms
Min.: 5
Max.: 65
F6-48
(02FE)
BACnet Device Object
Identifier 0
BAC Dev Obj Id 0
Sets the least significant word for BACnet.
Default: 0
Min.: 0
Max.: FFFF
F6-49
(02FF)
BACnet Device Object
Identifier 1
BAC Dev Obj Id 1
Sets the most significant word for BACnet.
Default: 0
Min.: 0
Max.: 3F
F6-50
(03C1)
DeviceNet MAC
Address
DN MAC Address
Selects the drive MAC address.
Default: 64
Min.: 0
Max.: 64
F6-51
(03C2)
DeviceNet
Communication Speed
DN Baud Rate
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Set from Network
4: Auto Detect
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Adjustable from network
4: Detect automatically
Default: 4
Range: 0 to 4
F6-52
(03C3) DeviceNet PCA Setting PCA Selection
Sets the format of the data set from the DeviceNet master to the
drive.
Default: 21
Min.: 0
Max.: 255
F6-53
(03C4) DeviceNet PPA Setting PPA Selection
Sets the format of the data set from the drive to the DeviceNet
master.
Default: 71
Min.: 0
Max.: 255
F6-54
(03C5)
DeviceNet Idle Mode
Fault Detection
DN Idle Flt Det
0: Stop
1: Ignore
0: Enabled
1: Disabled, no fault detection
Default: 0
Range: 0, 1
F6-55
(03C6)
DeviceNet Baud Rate
Monitor
DN BAUD RATE
MEM
0: 125 kbps
1: 250 kbps
2: 500 kbps
Verifies the baud rate running on the network.
0: 125 kbps
1: 250 kbps
2: 500 kbps
Default: 0
Range: 0 to 2
A.8 F: Option Settings
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
213
A
Parameter List